Figure 3.12 — Diagnostics
The Diagnostics page should look similar to the following. The
status line should say “Gen #x Off-Line” where x is the generator
number (Figure 3.13).
Figure 3.13 — Diagnostics Screen
Press the “Request MAN Mode Parallel” button and the button
name should change to “Cancel MAN Mode Parallel”. The genera-
tor will synchronize to the Bus if necessary and connect (Figure
3.14).
Figure 3.14 — Cancel MAN Mode Parallel
After the generator has connected to the Bus, the status will
change from “Gen #x Off-Line” to “Gen #x On-Line”. This could
happen immediately or take a few seconds while the generator
synchronizes to the Bus (Figure 3.15).
Figure 3.15 — MAN Mode Paralleling Status
After all the running generators are connected to the Bus, the
operator must determine what generator power is available and
what the load requirements are. If there is enough power available
for the given permissive to be active, the operator should manually
operate the permissive relay in the PM-SC control box according
to its priority of need. Manually operate the relay for about two (2)
seconds or until the ATS transfers to the emergency bus. (This
time is dependent on the ATS manufacturer requirement). The
operation of the relays is performed in one of two ways. See Figure
3.16 for explanation of how to manually operate relays.
If a generator should shutdown then the appropriate load needs to
be shed to allow the remaining system to function. The operator
must manually shed the required load to protect the MPS from
being overloaded and shutting down.
Operation
Summary of Contents for PowerManager 004975-2
Page 25: ...23 Notes...
Page 26: ...24 Notes...
Page 27: ...25 Notes...
Page 28: ...26 Installation Diagrams NEMA 1 Drawing No 0E7619 C...
Page 29: ...27 NEMA 1 Drawing No 0E7619 C Installation Diagrams...
Page 30: ...28 Installation Diagrams NEMA 3R Drawing No 0H3175 A...
Page 31: ...29 NEMA 3R Drawing No 0H3175 A Installation Diagrams...
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 47: ......
Page 48: ......