Troubleshooting
48
MGG155/210 Operating Manual
35319 C
Start blocking
This message means that a binary input with Startblocking function is active and engine
start is blocked. If active, NotReady state is shown on the controller screen and the mes-
sage appears in the Alarm list. As soon as input is deactivated, engine start is enabled
again.
Wrn CylTemp1-32
Warning protection on AI Cylinder temperature 1-32 is active. Check corresponding set-
points in the
Engine protect
group.
Wrn MCB fail
MCB failure was detected.
See
Circuit breakers operation sequence, GCB/MCB fail detection
chapter in IGS-NT-
x.y-Reference Guide.
Stp GCB fail
GCB failure was detected.
See
Circuit breakers operation sequence, GCB/MCB fail detection
chapter in IGS-NT-
x.y-Reference Guide.
Wrn BTB fail
BTB failure was detected.
See
Circuit breakers operation sequence, GCB/MCB fail detection
chapter in IGS-NT-
x.y-Reference Guide. It applies to BTB breaker too.
Wrn MGCB fail
MGCB failure was detected.
See
Circuit breakers operation sequence, GCB/MCB fail detection
chapter in IGS-NT-
x.y-Reference Guide. It applies to MGCB breaker too.
Sd Oil press B
Engine shut-down was activated by binary input with “Oil press” function (see LBI card in
GenConfig for information about source signal for this function).
Wrn RSync fail
Reverse synchronization failure indication, genset or group of gensets was not synchro-
nized to mains within
Sync/Load ctrl
:
Sync timeout
time.
Check setting of setpoints in the
Sync/Load ctrl
and
Volt/PF ctrl
groups. Frequency
regulation loop, Angle regulation loop and Voltage regulation loop are active during syn-
chronisation and you may need to adjust their setting.
Actual state of synchronization is visible on the controller measurement screen with syn-
chroscope where speed and voltage regulator's outputs, slip frequency and generator
and mains voltages can be observed during the synchronization process.
Stp Sync fail
Synchronization failure indication (alarm Sync timeout is active), genset or group of gen-
sets was not synchronized to mains/bus within
Sync/Load ctrl
:
Sync timeout
time.
Check setting of setpoints in the
Sync/Load ctrl
and
Volt/PF ctrl
groups. Frequency
regulation loop, Angle regulation loop and Voltage regulation loop are active during syn-
chronisation and you may need to adjust their setting.
Actual state of synchronization is visible on the controller measurement screen with syn-
chroscope where speed and voltage regulators' outputs, slip frequency and generator
and mains/bus voltages can be observed during the synchronization process.
Wrn Sync fail
Synchronization failure indication (alarm Sync timeout is active), genset or group of gen-
sets was not synchronized to mains/bus within
Sync/Load ctrl
:
Sync timeout
time.
Check setting of setpoints in the
Sync/Load ctrl
and
Volt/PF ctrl
groups. Frequency
regulation loop, Angle regulation loop and Voltage regulation loop are active during syn-
chronisation and you may need to adjust their setting.
Actual state of synchronization is visible on the controller measurement screen with syn-
chroscope where speed and voltage regulators' outputs, slip frequency and generator
and mains/bus voltages can be observed during the synchronization process.
BOC L1, L2 or L3 under
Generator L1, L2 or L3 voltage was under the
Gen <V BOC
limit for
Gen V del
time
.
Undervoltage protections are based on
Gener protect
:
Gen <V BOC
and
Gen V del
set-
points. This alarm is issued if voltage protections are based on phase to neutral voltages.
It means that
Basic settings
:
FixVoltProtSel
is set to PHASE-NEUTRAL.
Table 8 - Digital Controller List of Alarms
NT
Alarm/History
Record
Description