General Information and Setup
Owner’s/Installation Manual for SMM
7
Figure 2-3. SMM Sequence of Operations
Loa
d
is
OF
F
Start
Have five minutes
elapsed?
NO
NO
YES
Lo
cko
u
t sw
it
ch
is
s
e
t
to
:
LO
CKO
U
T
LO
A
D
LO
CKO
U
T
DI
SA
BLE
D
Is power
w
it
h
in
l
imi
ts
fo
r g
e
n
e
ra
to
r?
YES
N
O
Loa
d
is
OF
F
Has module
previously sh
e
d
the
lo
a
d
?
(Module now in
load-sh
e
d
r
e
co
ve
ry)
(2
)
Has module
previously locked out
the l
o
a
d
? (Module now
in lockout recovery)
NO
YES
Ha
ve
l
o
a
d
-sh
e
d
recovery time a
n
d
m
o
du
le
p
ri
o
ri
ty
time e
la
p
sed
?
(1
)
YES
N
O
W
as lo
cko
u
t
recovery o
p
e
ra
ti
o
n
su
cce
s
sf
u
l?
YES
NO
YES
NO
No
te
s:
(1
) R
e
fe
r to
th
e
P
ri
o
ri
ty
S
e
tt
in
g
s
ta
b
le
fo
r
in
fo
rm
a
ti
o
n
o
n
r
e
c
o
v
e
ry
p
ri
o
ri
ty
ti
m
e
s
.
(2
)
If
t
h
e
mo
du
le
d
e
te
ct
s
a
g
e
n
e
ra
to
r
o
v
e
rl
o
a
d
during a load-shed recovery
,
th
e
m
o
du
le
w
ill
a
g
a
in
sh
e
d
the
lo
a
d
f
o
r up
t
o
30
m
inu
te
s.
Loa
d
i
s
O
N
Loa
d
i
s
O
F
F
Loa
d
i
s
O
N
Is power w
it
h
in
no
m
ina
l f
o
r ut
ili
ty
?
Is power w
it
h
in
no
m
ina
l f
o
r ut
ili
ty
?
YES
NO
YES
Lo
cko
u
t sw
it
ch
is
s
e
t
to
:
LO
CKO
U
T
LO
A
D
LO
CKO
U
T
DI
S
A
B
L
E
D
0071
11