Automatic Standby Generator Owner’s Manual
4.2 — Service Schedule
ATTENTION: All service work must be performed by a qualified service person only.
4.2.1 — Maintenance Log
1. Battery inspection and charge check (recommended every year (1) for the life of the battery)
NOTE: Check electrolyte level (unsealed batteries only) every 6 months.
Dates Performed:
2. Oil, oil filter and air filter replacement (recommended after the first 20 hours after installation and every 100 hours or 6 months, whichever
occurs first)
NOTE: Spark plug replacement (recommended every 1 year or 300 hours, whichever occurs first).
Dates Performed:
System Component
Procedure
Frequency
X = Action
R= Replace as Necessary
* = Notify Dealer if Repair is Needed
Inspect
Change
Clean
W = Weekly
M = Monthly
Y = Yearly
Fuel
Fuel lines and connections*
X
M
Lubrication
Oil level
X
M or 24 hours of continuous operation
Oil
X
6 M or 100 hours of operation**
Cooling
Enclosure louvers
X
X
W
Battery
Remove corrosion, ensure dryness
X
X
Y
Clean and tighten battery terminals
X
X
Y
Check charge state
X
X
Y
Electrolyte level (unsealed batteries only)*
X
X
Every 6 M
Engine and Mounting
Air cleaner
X
X
X
3 M / 50 hours - clean / 1 Y / 300 hours - replace
Spark plug
X
X
6 M or 100 hours - inspect / 1 Y or 300 hours - change
Valve Clearance
X
1 Y or 300 hours***
General Condition
Vibration, Noise, Leakage*
X
M
* Contact the nearest Dealer for assistance if necessary.
** Change oil after the first 20 hours of operation or 1 month. Continue to check at intervals of 100 hours or 6 months, whichever occurs first. Severe duty oil
drain intervals: In cold weather conditions (ambient below 40
º
F/4.4
º
C) change engine oil every 6 months or 50 hours of operation to prevent accumulation
of water in the oil. If the unit will be operated continuously in hot ambient conditions (ambient above 85
º
F/29.4
º
C) or operation in an extremely dusty or dirty
environment change the engine oil every 3 months or 50 hours of operation to prevent oil breakdown.
*** Check valve clearance after the first 20 hours of operation. Continue to check at intervals of 300 hours.
Summary of Contents for 7 kW PowerPact
Page 4: ...iv This page intentionally left blank...
Page 20: ...16 Automatic Standby Generator Owner s Manual This page intentionally left blank...
Page 32: ...28 Automatic Standby Generator Owner s Manual This page intentionally left blank...
Page 34: ...30 Automatic Standby Generator Owner s Manual This page intentionally left blank...
Page 35: ......