We reserve the right to modify the characteristics of the equipment supplied without notice or as part of the continued development of our products. 

 
 

              4 

 

Undo securing nuts on heater flange and remove flange complete with Electric Immersion 
Heater. 

 

 

Inspect heater elements and de-scale if necessary. 

 

Inspect interior of cylinder and clean out any debris. 

 

Re-assemble using a new gasket on the flange and tighten bolts. 

 

Re-connect Immersion Heater wiring. 

 

Refill system and check for leaks around flange. 

 

Replace Electric Immersion Heater cover. 

 

Carry out annual inspection as above. 

 

THE OPENING TEMPERATURE OF THE P & T VALVE IS 90 

o

 
 

The position of the tundish shall be visible to the occupants and shall be positioned away from 
any electrical devices. 

 
 

See   Fig  no. 7, Page 13 of EBS manual for tundish position and discharge pipe. 

 

 

The connection details are shown on Page 13, drawing no. Fig 7.  The relief valve connections 

should not be altered or used for any other type of connection. 

 
 

Details of the discharge pipe and installation requirements can be seen on drawing no. Fig 7, 
Page 13 and Table 2, Page 6. 

 

Before connecting pipework, fit the Siemens safety shut off zone valve to the primary return 

outlet. 

 
 

The incoming cold water supply pipe must be fitted with a stopcock before the cold water 
unvented kit.  A drain cock must be fitted between the unvented kit and the cylinder. 

 

 

The unit should be carried into position within its packaging and on its pallet. 

 
 

Once in position, the pallet should be removed. 

 

The cylinder should be installed on a floor designed to take the weight of the cylinder when full 

of water.  Each litre of water weighs 1 Kg.  The actual water content of each cylinder should 
be added to the cylinder weight to obtain the total weight of the cylinder when full to ascertain 
if the floor is of suitable construction. 

 
 

300mm clearance should be left on the top of the cylinder for access to the anode and 
inspection door. 

 
 

No valve shall be fitted between the cylinder and the expansion valve. 

 

Our optional immersion heater control panel is unique in that you cannot heat the water using 

the boiler and the immersion on at the same time.  The rocker switch on the control panel 
either sends power to the immersion heater or to the boiler safety circuit.  So, if the immersion 
is on, the valve closes and the boiler cannot supply hot water to the cylinder. 

 
 

No other immersion, other than our EBS Immersion Heater should be used on our EBS 
cylinders. 

 
 

The EBS range of cylinders is ideally suited for connection to our Geminox boilers to match 
the coil ratings.  However, connection to non – Geminox boilers can be carried out if required.  
Please contact our Technical Department for installation assistance on + 44 (0)1372 722277. 

 

To flush through the cylinder, simply open inspection door, disconnect unvented kit and flush 

through the cylinder to the drain by using a hose through the inspection door. 

 
         

 

100 

  

 

300 

Results of supply temperature 1-50 – 220   

 

19 mins  

26 mins 

 

Summary of Contents for EBS 100

Page 1: ...We reserve the right to modify the characteristics of the equipment supplied without notice or as part of the continued development of our products 0...

Page 2: ...100 313 531 THI 0 9 9 C BS 300 9 1 4 4 37 7 86 153 476 693 THI 2 13 C BS 100 13 5 6 5 15 2 19 35 160 483 THI 2 13 C BS 150 13 5 6 5 21 3 29 52 241 564 THI 2 13 C BS 200 13 5 6 5 26 7 38 68 313 636 TH...

Page 3: ...ex Page 2 Index 3 WRc approved documentation Contains important information please read 6 Important notice please read 7 Hydraulic connections for cylinders 9 Cylinders with immersion heaters 11 Cylin...

Page 4: ...ater 35 kg 45 kg 55 kg 70 kg CONNECTIONS Cold Water Inlet Domestic Hot Water Flow Hot Water Secondary Returns Primary Flow from Boiler Primary Return to Boiler 2 MAINTENANCE WARNING BEFORE COMMENCING...

Page 5: ...it should be carried into position within its packaging and on its pallet Once in position the pallet should be removed The cylinder should be installed on a floor designed to take the weight of the c...

Page 6: ...s both hot and cold water and any other water discharge points showers etc Check operation of expansion relief valve on Cold Water Supply Kit by lifting manual release lever and discharging water Chec...

Page 7: ...See Table 2 below for sizing details of safety discharge pipe from our tundish Table 2 Sizing of copper discharge pipe D2 for common temperature relief valve outlet sizes Valve Outlet Size Minimum Si...

Page 8: ...t on the cold water supply The Unvented kit contains pressure reducing valve non return valve pressure relief valve and optional use balanced cold water connector It is good practice to fit the unvent...

Page 9: ...right to modify the characteristics of the equipment supplied without notice or as part of the continued development of our products 8 Fig 3 1 Unvented kit for EBS cylinders Fig 4 1 Unvented kit for...

Page 10: ...without notice or as part of the continued development of our products 10 11 Whilst in heating cycle using the immersion heater the Green selector switch LED will illuminate and extinguish once desir...

Page 11: ...low CPC 7 The desired temperature setting should now be set using the controls on the top of the cylinder or should be left on maximum if the hot water is controlled via our boiler controls Technical...

Page 12: ...We reserve the right to modify the characteristics of the equipment supplied without notice or as part of the continued development of our products 13 PRESSURE TEMPERATURE RELIEF VALVE...

Page 13: ...tics of the equipment supplied without notice as part of our continued development of products IMPORTANT This drawing to be read in conjunction with the full installation manuals supplied SECONDARY RE...

Page 14: ...We reserve the right to modify the characteristics of the equipment supplied without notice or as part of the continued development of our products 15...

Page 15: ...We reserve the right to modify the characteristics of the equipment supplied without notice or as part of the continued development of our products 16...

Page 16: ...ND BUILDING CONTROL INSPECTOR PRIOR TO INSTALLATION 300 mm minimum from Tundish to Bend Building Regulations requirements 200 mm minimum height above HepvO Valve 300 mm between pipe clips PIPE CLIP TO...

Reviews: