13.1.2.2 Electrical connection
1
3
2
1
3 2
6
5
4
Plug assignment X1
Plug assignment X2
Pin
Description
Pin
Description
1
L1 / Uv+, direction of travel CLOSED
1
Change-over contact limit switch CLOSED
2
L1 / Uv+, direction of travel OPEN
2
Make contact limit switch CLOSED
3
N / Uv-, neutral conductor
3
Break contact limit switch CLOSED
PE, protective earth conductor
4
Break contact limit switch OPEN
5
Make contact limit switch OPEN
6
Change-over contact limit switch OPEN
PE, protective earth conductor
N / L- signals in the unit are separated.
The potential must be assigned by the user.
When the OPEN and CLOSED switches are operated simultaneously the actuator "CLOSES".
13.1.2.3 Connection diagram
1
3
2
L1/Uv+
N/Uv-
PE
External wiring
Direction
switch
Motor protection switch
recommended
CLOSED
OPEN
1
3 2
6
5
4
1
4 2
1
4
2
OPEN
CLOSED
Additional
limit switches
Connection assignment X1
Connection assignment X2
13.1.3 On/Off actuator with potentiometer output, with relay (code 0P), 24 V DC (code C1)
13.1.3.1 Position of the connectors
X2
X1
X2
X1
X2
X1
Actuator version 2070
Actuator version 4100, 4200
GEMÜ R478 Tugela
www.gemu-group.com
93 / 108
13 GEMÜ 9468 electrical connection