7.7 Electrical data
Supply voltage:
24 V DC
Tolerance ± 10 %
Operating time:
Actuator size 1A
DN 15: 3.5 s
DN 20: 5.5 s
DN 25: 6.0 s
DN 32: 8.5 s
DN 40: 8.5 s
DN 50: 8.5 s
Actuator size 3A
DN 32: 8.5 s
DN 40: 9.5 s
DN 50: 12.0 s
Close tight current / rated
current:
Actuator size 1A: 1.1 A
Actuator size 3A: 2.3 A
Starting current / max-
imum current:
Actuator size 1A: 2.4 A
Actuator size 3A: 4.5 A
Standby current con-
sumption:
approx. 10 mA
7.7.1 Digital input signals
Input voltage:
max. 30 V DC
High level:
≥ 18 V DC
Low level:
≤ 5 V DC
7.7.2 Emergency power supply module
Charging current:
Actuator size 1A: max. 0.16 A
Actuator size 3A: not available
Charging time:
approx. 13 min
Service life:
Guide value at 25 °C ambient temperature, approx. 3 years
www.gemu-group.com
12 / 29
GEMÜ 519 eSyLite
7 Technical data