background image

www.gemu-group.com

15 / 20

GEMÜ 0326

NOTICE

Electrical connection with the connecting cable integ-

rated into the solenoid coil (cable ends suitable for screw

clamp connections) in the safe area or in the potentially

explosive area with permissible equipment protected

from explosion (e.g. terminal box with type of ignition pro-

tection Increased Safety "e" as per EN 50019).

When screwing in the connecting wires, make sure that

the cable ends fit completely into the connecting clamp.

Connecting wires and cables should not be bent sharply

in order to avoid short circuits and breaks.

11.2 M12 plug (code 02, 03)

11.2.1 Pin assignment

1

4

3

2

5

Plug assignment X1 (A-coded)

Pin

Signal name

1

n.c.

2

n.c.

3

Uv, GND

4

Uv, 24 V DC supply voltage

5

n.c.

11.3 Manual override (option)

Fig. 4: Manual override

The pilot solenoid valves are equipped with a manual override

as an option.

Only actuate the manual override in case of malfunction!

To activate / lock the manual override:

1. Turn red button 90° clockwise with a screw driver.
2. To unlock turn it 90° anti-clockwise with a screwdriver.

12 Commissioning

 CAUTION

Protect against leakage!

Check the tightness of the media con-

nections prior to commissioning!

Provide precautionary measures

against exceeding the maximum per-

mitted pressures caused by pressure

surges.

Prior to cleaning or commissioning the plant:

1. Check the tightness and the function of the pilot solenoid

valves.

2. If the plant is new and after repairs blow out the piping

system with a fully opened pilot solenoid valve (to remove

any harmful foreign matter).

Cleaning:

The plant operator is responsible for selecting the cleaning

material and performing the procedure.

12 Commissioning

Summary of Contents for 0326

Page 1: ...GEM 0326 Electrically operated pilot solenoid valve Operating instructions EN further information webcode GW 0326...

Page 2: ...rights including copyrights or industrial property rights are expressly reserved Keep the document for future reference GEM Gebr M ller Apparatebau GmbH Co KG 30 06 2021 www gemu group com 2 20 GEM 0...

Page 3: ...Transport 12 9 3 Storage 12 10 Installation 12 11 Electrical connection 13 11 1 Plug design A 14 11 2 M12 plug code 02 03 15 11 3 Manual override option 15 12 Commissioning 15 13 Troubleshooting 16 1...

Page 4: ...flows through the GEM product 1 4 Warning notes Wherever possible warning notes are organised according to the following scheme SIGNAL WORD Type and source of the danger Possible symbol for the specif...

Page 5: ...stood by the responsible personnel 6 Define the areas of responsibility 7 Observe the safety data sheets 8 Observe the safety regulations for the media used During operation 9 Keep this document avail...

Page 6: ...near the pneumatic components to be controlled The body is made of plastic The coil is plastic encapsulated 5 1 Product without ATEX code 06 08 09 The product is not intended for use in potentially e...

Page 7: ...reen LED suppression diode only for 24V DC version 09 10 Option Code Without 00 10 Continuation of Option Code ATEX only electrical connection 05 only control function normally closed 01 Manual overri...

Page 8: ...Connection for GEM battery rail 5 Valve body solenoid material 74 PA polyamide 6 Seal material 4 FPM 7 Control function 1 Normally closed NC 8 Voltage Frequency C1 24 V DC 9 Electrical connection 01...

Page 9: ...Operating pressure 0 10 bar Flow rate Control function Normally closed code 1 70 l min Normally open code 2 40 l min 7 4 Product compliance Explosion protection ATEX 2014 34 EU order code Option ATEX...

Page 10: ...0580 Duty cycle Continuous duty Max perm ripple 20 Electrical connection type Plug design A Cable diameter 8 to 10 mm Optional M12 plug cable socket Optional ATEX version with 3 m cable H05V2V2 F 3G1...

Page 11: ...5 30 40 5 4 2 G1 4 81 5 20 25 52 77 49 8 12 5 M4 Z Number of valve seats valves maximum 10 valves possible Female thread M4 for the connection of the potential equalisation acc to ATEX Blanking plate...

Page 12: ...lve prior to the installation See chapter Technical data 10 1 Installation WARNING The equipment is subject to pressure Risk of severe injury or death Depressurize the plant Completely drain the plant...

Page 13: ...ction DANGER Risk of electric shock Risk of injury or death if operating voltage is higher than safe extra low voltage Electric shock can cause severe burns and fatal injury Work on electrical connect...

Page 14: ...Screw plug 2 to solenoid with retaining screw 1 max 0 3 Nm 11 Close cable entry 6 Fig 3 Rear of terminal block Item Name 1 Supply voltage 2 Supply voltage 3 Not connected Earth 11 1 Plug design A 11 1...

Page 15: ...Manual override option Fig 4 Manual override The pilot solenoid valves are equipped with a manual override as an option Only actuate the manual override in case of malfunction To activate lock the ma...

Page 16: ...pilot solenoid valve doesn t close or doesn t close fully Return spring faulty Replace the pilot solenoid valve Dirt in the valve body Clean or replace valve body Manual override activated Unlock the...

Page 17: ...valves dependent on the operating conditions and the poten tial danger in order to prevent leakage and damage The valve also has to be checked for wear in the corresponding inter vals 15 Disassembly D...

Page 18: ...ve We GEM Gebr M ller Apparatebau GmbH Co KG Fritz M ller Stra e 6 8 74653 Ingelfingen Criesbach Germany declare that the product listed below complies with the directives named above Description of t...

Page 19: ...sion protection designation Gas II 2G Ex mb II T4 Dust II 2D Ex tD A21 IP65 T130 C Type examination certificate PTB 03 ATEX 2018 X Explanations For special conditions or operation limits see chapter C...

Page 20: ...GEM Gebr M ller Apparatebau GmbH Co KG Fritz M ller Stra e 6 8 74653 Ingelfingen Criesbach Germany Phone 49 0 7940 1230 info gemue de www gemu group com Subject to alteration 06 2021 88660085 88660085...