GEMÜ 0326
11 Electrical connection
Plug form A
(DIN EN 175301-803)
6
4
5
1
2
3
Fig. 2: Electrical connection of plug
1. Disconnect the plant from power supply.
2. Unscrew retaining screw
1
.
3. Pull off plug
2
with terminal block
3
from solenoid.
4. Press terminal block
3
carefully out of plug
2
.
5. Unscrew cable entry
6
.
6. Remove pressure ring
4
and gasket
5
.
7. Insert cable through cable entry
6
, pressure ring
4
, gasket
5
and plug
2
.
8. Connect the cable.
9. Insert terminal block
3
again in the plug
2
until it audibly
clicks in position.
10. Screw plug
2
to solenoid with retaining screw
1
(max.
0.3 Nm).
11. Close cable entry
6
.
Fig. 3: Rear of terminal block
Item
Name
1
Supply voltage
2
Supply voltage
3
Not connected
Earth
11.1 Plug design A
11.1.1 Without bridge rectifier (code 00, 01, 03, 05, 08, 09)
Control function 1 (NC), AC/DC voltage
control function 2 (NO), DC voltage
L PE N
+ PE GND
DC supply voltage:
NC/NO valves
AC supply voltage:
Plug form A
Solenoid valve
with plug form A
11.1.2 With bridge rectifier (code 06, 09)
Control function 2 (NO), AC voltage
L PE N
AC supply voltage:
NO valves
Plug form A with bridge rectifier
Solenoid valve
with plug form A
11.1.2.1 ATEX version (DC version)
Solenoid housing
Blue
Brown
Green/yellow
11.1.2.2 ATEX version (AC version)
Solenoid housing
Blue
Brown
Green/yellow