AIR HEATER PELLET STOVE BY GEKASMETAL
Page 18
After you connect the appliance to electric current, turn the switch, on the back of the appliance, on position 1. On the screen the following appear:
Name - type of the appliance and operation program (i.e.
Air 1
).
With the application of electric power voltage the appliance performs a
CHECKING
in case there is fire in the combustion chamber. On the screen appears the following
image:
If there is fire and the fume temperature is higher than the temperature of
”
Down Error
”
, then the appliance starts automatically and moves to
<OPERATION>
phase,
without saving activation to the memory.
If there is fire and the fume temperature is lower than the temperature of
”
Down Error
”
,
then the appliance moves to the
<FINAL CLEANING>
phase, if existing, and then to
the
<INERTIA>
phase, without saving activation to the memory.
If there is
no
fire, then the controller moves to the
<INERTIA>
phase or the
<SHUTDOWN>
phase, depending on whether it was enabled or disabled before the interruption of
electrical supply voltage.
During the first ignition, it is possible that the appliance will move to the
<SHUTDOWN>
phase, due to required quality inspections and testings that have been performed in the
factory.
Holding down the
ON/OFF(ESC)
button the operation phase appears on the screen:
<INITIAL CLEANING>
During this phase the appliance uses the combustion fan to clean the combustion chamber from remaining materials. The combustion chamber fan operates in this phase.
Then, the appliance, automatically, moves to operation phase:
<PRE-HEATING>
During this phase the ignition resistance is being enabled, in order to prepare the next phase.
<FUELING>
During this phase the fueling of the combustion chamber with pellets is being enabled, in order to create a stock for the ignition. Ignition resistance is enabled.
<FLAME HOLD>
The appliance enters this phase after fueling. The control system remains in this phase for some time.