Gekasmetal AMANDA User Manual Download Page 12

                                                                                                                                          

                                                                                                                       

 

AIR HEATER PELLET STOVE BY GEKASMETAL 

                                                                                  

 

Page 12

 

 

a

c

b

90°

 

Area for the height of the mouth with inclination ( ß >10°) 

REFERENCE 

DESCRIPTION 

DISTANCE IN mm 

Calculated distance 90° from the roof surface 

1300 

Height over the ridge of the roof. 

500 

The mouth of a pipe-in-pipe system should not be near obstacles that may create swirling zones or obstruct proper fume discharge and roof maintenance activities.  Check for 
other ridges or skylights and attics.  

PRODUCT REQUIREMENTS FOR THE FUME EXTRACTION SYSTEM   

Temperature class 

In case o a pellet appliance temperature classes lower than  T200 are not allowed.

 

Soot fire resistance class 

For the fume extraction system, which is controlled by appliances that use solid fuel, soot fire resistance is required. Therefore, the definition should be set with the letter G 
accompanied to the distance from combustible materials in mm.  (according to EN 14785 (2006) 

In case of pellet appliances the fume extraction systems should have leak-tightness, if they use elements of double definition (G and O, with or without  elastomeric sealing). 
For the connection of the appliance with the fireplace, minimum speed XX in mm should be kept, defined by G. In case of soot fire, make sure you will restore initial 
conditions (replacement of gaskets and other damaged components and cleaning of those still appropriate for use). 

Ignition testing  

The operation of the appliance should be controlled with ignition testing, or  

 

For appliances with mechanical supply, the ignition phase should be finished. Proper function should be verified for at least the next 15 minutes, as well as proper 
deactivation, 

 

For appliances inserted in an installation of heating with hot water (thermal fireplaces, thermal stoves), inspection should be performed on the total hydraulic 
system.  

Coatings and finishings 

Coatings and finishings should be applied only after proper function of the appliance has been verified, according to the defined ways. 

 

 

4.

 

CLEANING AND MAINTENANCE 

Summary of Contents for AMANDA

Page 1: ...AIR HEATER PELLET STOVE BY GEKASMETAL Page 1 AMANDA 9KW Manual...

Page 2: ...METAL The pellet stove is an ideal heating solution It uses advanced technology and it has been constructed according the highest standards with modern design that allows you to enjoy your heat with...

Page 3: ...r operator of the appliance should read and fully comprehend the content of this manual before attempting any use of it Mistakes or incorrect adjustments may cause dangerous conditions or and poor fun...

Page 4: ...ext ignition Do not clean the product with water Water could leak into the appliance and destroy the electric insulation causing electrocution Do not stand in front of the appliance for a long time Av...

Page 5: ...th the appliance The term guarantee refers to the free of charge replacement or repair of the parts of the appliance which are admitted as defective by construction RESTRICTIONS The above mentioned gu...

Page 6: ...the European market and guarantee that the following characteristics are being retained Thermal value 4 9 kWh kg Humidity max 10 of its weight Ash percentage max 0 5 of its weight Diameter 5 6 mm Len...

Page 7: ...here should be an ventilation opening The air pipes should comply with following requirements Be protected with racks metal nets etc without reducing however the useful part Be constructed in such way...

Page 8: ...ggested CONNECTION TO ELECTRIC NETWORK Before the connection of the appliance to electric network check if the electrical installation is equipped with ground and differential switch according to regu...

Page 9: ...cross flammable materials the above instructions should be followed SYMBOL DESCRIPTION HEIGHT mm b Minimum distance from combustible materials from the inside of the ceiling floor wall 500 B Minimum d...

Page 10: ...pe should allow the retrieval of soot it should be cleaned and be inspected after being dismantled or through the inspection openings if it is not accessible from the inside of the appliance ADDITIONA...

Page 11: ...ns only with negative pressure in relation to the environment and should be according to EN 14785 2006 Flue terminals The flue terminals should comply with the following requirements They should be se...

Page 12: ...N 14785 2006 In case of pellet appliances the fume extraction systems should have leak tightness if they use elements of double definition G and O with or without elastomeric sealing For the connectio...

Page 13: ...to remove it The glass should be cleaned using a dry cloth If needed you can use water and a soft detergent only if the glass is cold Once in a month clean the area behind the ash tank by removing th...

Page 14: ...that performed the actions of inspection or and maintenance along with contact information date and signature of the technician 5 TECHNICAL CHARACTERISTICS MODEL WOOD PELLET STOVE AMANDA DIMENSIONS Hx...

Page 15: ...causes exit without recording the value During the processing of text it causes exit without recording the text Prolonged press Switches off the boiler performing all necessary actions ignition combu...

Page 16: ...th Minus button it changes the current indications screen Main Screen Entries Screen Exits Screen 4 Minus Button Decrease and navigation button Single press Enables the screen for room temperature set...

Page 17: ...it should firstly be activated The control system is considered activated when it is at any phase except for the phase SHUTDOWN If it is deactivated the indication on the screen is SHUTDOWN If it is a...

Page 18: ...re then the controller moves to the INERTIA phase or the SHUTDOWN phase depending on whether it was enabled or disabled before the interruption of electrical supply voltage During the first ignition i...

Page 19: ...nd the combustion fans are adjusted automatically in order to achieve the desirable operation temperature Manually When a manual program has been selected then the control system is not enabled On the...

Page 20: ...he control system in this phase and for a small period of time preserve their former speed After this period of time and for the rest of the phase the combustion fan functions with maximum speed The s...

Page 21: ...The entry signals remain activated The system does not return in function if the error has not been removed by the user 22 Low Fumes Fume temperature below the limit for a specific period of time The...