80990B_MHW_CAN-IO_12-2016_ENG
FAST DIGITAL INPUT
Period measurer / impulse
duration measurer output format
TYPE: DINT
Resolution: 32 bit (0 ... 21,4 s)
LSB: 10 ns
Frequency measurer output
format
TYPE: DINT
Resolution: 32 bit (0 ... 500 kHz)
LSB: 0,1 Hz
Protections
Polarity inversion
Overvoltage: max 1 kV per 1 ms
Electric insulation
Channel-channel: no
Channel-bus: 2 kV
Main functions
6 one-way incremental encoders [A] max;
2 one-way incremental en zero notch [A+Z] max;
2 two-way incremental encoders [AB] max;
2 two-way incremental en zero notch [AB+Z] max;
Max 6 count forward [Counter]
Auxiliary functions
Period measurer
Frequency measurer
Duty-cycle measurer
Positive/negative impulse measurer
THERMOCOUPLE
TEMPERATURE INPUT
Max number
10 (orderable in groups: 2, 4, 6, 8, 10)
Type
Thermocouple J, K, R, S, T, E, B, L, N
Type of connection
2 wires (insulated and non-insulated)
Through band
0,5 Hz
Input impedance
> 1 MΩ
Sampling time
(for all channels)
100 ms
Resolution
0,1 °C / °F
Max error @ 25 °C
±0,5% scale bottom
Thermocouple use interval
(scale)
J: 0 … 1000 °C / 32 … 1830 °F
K: 0 … 1300 °C / 32 … 2372 °F
R: 0 … 1750 °C / 32 … 3182 °F
S: 0 … 1750 °C / 32 … 3182 °F
T: -200 … 400 °C / -392 … 752 °F
E: -100 … 750 °C / -212 … 1382 °F
B: 0 … 1820 °C / 32 … 3308 °F
L: -200 … 400 °C / -392 … 752 °F
N: 0 … 1300 °C / 32 … 2372 °F
THERMO RESISTANCE
TEMPERATURE INPUT
Max number
10 (orderable in groups: 2, 4, 6, 8, 10)
Type
Thermo resistance PT100 or PT1000
Type of connection
2 or 3 wires
Through band
0,5 Hz
Input impedance
PT100: 12 kΩ
PT1000: 120 kΩ
Sampling time
(for all channels)
100 ms
Resolution
0,1 °C / °F
Max Error @ 25 °C
±0,5% scale bottom
Use interval (scale)
-200…850 °C / -392…1562 °F
Protections
Polarity inversion: yes
Overvoltage: max 1 kV per 1 ms
Electric insulation
Channel-channel: no
Channel-bus: 2 kV