![gefran CAN-IO Installation And User Manual Download Page 12](http://html.mh-extra.com/html/gefran/can-io/can-io_installation-and-user-manual_2205693012.webp)
12
80990B_MHW_CAN-IO_12-2016_ENG
RELAY OUTPUT,
SINGLE CONTACT
Max number
8 (orderable in groups: 2, 4, 6, 8)
Type
Single N.O. contact
Rated voltage
30 Vdc / 250 Vac
Max current
5 A
Mechanical duration
20 x 10
6
operations
Contact duration
70.000 operations
Protections
Overvoltage: max 430 V @ 1 mA
Electric insulation
Channel-channel: yes
Channel-bus: 3 kVrms
RELAY OUTPUT,
EXCHANGE CONTACT
Max number
4 (orderable in groups: 2, 4)
Type
exchange contact N.O., N.C.
Rated voltage
30 Vdc / 250 Vac
Max current
5 A
Mechanical duration
20 x 10
6
operations
Contact duration
2 A: 300.000 operations
5 A: 70.000 operations
Protection
Overpressure: max 430 V @ 1 mA
Electric insulation
Channel-channel: yes
Channel-bus: 3 kVrms
PWM OUTPUT
Max number
8 (orderable in groups: 2, 4, 6, 8)
Composition
Every 8 outputs a power wire
Type
Current emission
Rated voltage
25 Vdc ±25%
Max output current
Single output: 1 A
Group of 8 outputs: 8 A
Output configuration
PWM
Frequency
PWM output
Duty cycle: resolution 0.01%
Frequency: resolution 0.01 Hz
Max frequency: 5 kHz
Frequency output
Duty cycle: resolution 50%
Frequency: resolution 0.01 Hz
Max frequency: 50 kHz
Output format
Type: INT
Resolution: 13 bit (-4096 … 4095)
LSB: 2,44 mV
Switch delay
0
⇒
1: 1,5 μs
1
⇒
0: 1 μs
Protections
Short circuit
Overload : I ≥ 1.4 A
Overtemperature
Overvoltage: max 1 kV per 1 ms
Electric insulation
Channel-channel: no
Channel-bus: 2 kV