ADV200 SP • Quick start up guide - Specification and installation
33
RS485
(XS)
RS485
RS232
PCI-COM
(S560T)
Industrial PC
(with RS485)
PC with RS232 port
PC with USB port
RS485
(XS)
RS485
(XS)
Shielded cable with connectors,
4.5 mt (8S864C), 10 mt (8S874C)
Shielded cable with connectors,
4.5 mt (8S864C), 10 mt (8S874C)
RS485
USB
Serial converter USB / RS485
5 mt (8S8F64)
Figure 5.4.1.2: RS485 connection to the PC
Connection of an industrial PC with RS485
The following are required for connection:
• shielded cable for the
XS / RS485
connection (see figure 5.4.1.
2), code 8S864C.
Connection to a PC with RS232 port
The following are required for connection:
• an optional
PCI-COM
(or PCI-485) adapter, code S560T.
• shielded cable for
XS / PCI-COM
(or PCI-485) connection, code 8S864C, see figure 5.4.1.
2 .
Connection to a PC with USB port
The following is required for connection:
• an optional
USB/ RS485
adapter, code 8S8F64
, see figure 5.4.1.
2 .
5.4.2 Drive / RS485 port point-to-point connection (with insulation)
To make the connection with galvanic isolation, the
OPT-RS485-ADV
optional card is required.
The card is equipped with a 9-pin D-SUB male receptacle connector which must be inserted in the
XS
connec-
tor of the ADV200 SP drive.
Connect terminals 1, 2 and 4 to the serial line as shown in the figure below; for the connection from the serial
line to the PC, the adapters indicated in paragraph 5.4.1 must be used.
XS
Terminal
1
2
3
4
Name
TxA /RxA
TxB /RxB
Reserved
EQP (Equipotentiality)
Switch
S1
Function
Closing of terminations
Figure 5.4.2.1: OPT-RS485-ADV card
Summary of Contents for ADV200 SP Series
Page 105: ......