Logic inputs
Ri = 4,7K
Ω
(24V, 5mA) or no-voltage contact
Protocol
Gefran CENCAL / MODBUS
Serial interface (optional)
RS485, isolated
Analogue retransmission signal
10V/20mA Rload max 500
Ω
resolution 12 bit
Transmitter power supply
10 / 24Vdc, max 30mA short-circuit protection
Type of relay contact
NO (NC), 5A, 250V/30Vdc cos
ϕ
=1
Logic output for static relays
24V ±10% (10V min at 20mA)
Cycle time
0...200 sec
Main output type
relay, logic, continuous (0....10V / 4...20mA)
Control outputs
on / off, continuous
Maximum power limit heat / cool
0,0...100,0 %
°C / °F selection
configurabile da tastieraconfigurable from faceplate
Linear scale ranges
-1999 to 9999 with configurable decimal point position
Controls
PID, Self-tuning, on-off
pb - dt - it
0,0...999,9 % - 0,00...99,99 min - 0,00...99,99 min
Action
Heat / Cool
Softstart
0,0...500,0 min
Configurable alarms
Up to 3 alarm functions assignable to an output,
configurable as: maximum, minimum, symmetrical,
absolute/deviation, LBA, HB
Fault power setting
-100,0...100,0 %
Automatic blanking
Displays PV value, optional exclusion
Alarm masking
- exclusion during warm up
- latching reset from faceplate or external contact
Optional ammeter input
T.A. 50mAac, 50/60Hz, Ri = 10
Ω
Faceplate protection
IP65
Working / Storage temperature range
0...50°C / -20...70°C
Relative humidity
20 ... 85% non-condensing
Installation
Panel, plug-in from front
Weight
160g for the complete version
Power supply (switching type)
(std) 100 ... 240Vac ±10%
(opt.) 20...27Vac/dc ±10%;
50/60Hz, 8VA max
Safety
detection of short-circuit or opening of probes, LBA
alarm, HB alarm
RTD type (scale configurable within indicated
range, with or without decimal point) (ITS90)
Max line resistance for RTD
DIN 43760 (Pt100), JPT100
20
Ω
Cold junction error
0,1° / °C
PTC type / NTC Type
990
Ω
, 25°C / 1K
Ω
, 25°C
600
CONTROLLER
SOFTWARE VERSION 1.1x
code 80336B / Edition 05 - 10/03
USER’S MANUAL
For correct and safe
installation, follow the
instructions and
observe the warnings
contained in this
manual.
Type TC Thermocouples
(ITS90)
Display
2 x 4 digits, green, height 10 and 7mm
Keys
4 mechanical keys (Man/Aut, INC, DEC, F)
Accuracy
0.2% full scale ± 1 digit at 25°C room temperature
Main input (settable digital filter)
TC, RTD, PTC, NTC
60mV,1V Ri
≥
1M
Ω
; 5V,10V Ri
≥
10K
Ω
; 20mA Ri=50
Ω
Sampling time 120 msec.
1 • INSTALLATION
• Dimensions and cut-out; panel mounting
Panel mounting:
To fix the unit, insert the brackets provided into the seats on either side of the
case. To mount two or more units side by side, respect the cut-out dimensions
shown in the drawing.
CE MARKING: EMC conformity (electromagnetic compatibility) with EEC Directive
89/336/CEE with reference to the generic Standard CEI- EN61000-6-2 (immunity in
industrial environments) and EN50081-1 (emission in residential environments). BT
(low voltage) conformity respecting the Directive 73/23/CEE modified by the Directive
93/68.
MAINTENANCE: Repairs must be done only by trained and specialized personnel. Cut
power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.).
Use of these solvents can reduce the mechanical reliability of the device. Use a cloth
dampened in ethyl alcohol or water to clean the external plastic case.
SERVICE: GEFRAN has a service department. The warranty excludes defects caused
by any use not conforming to these instructions.
2 • TECHNICAL SPECIFICATIONS
!
18
99
10
45
45
48
70
70
63
48
FUNCTION
CABLE TYPE
LENGTH
Power supply cable
1 mm
2
1 m
Relay output cable
1 mm
2
3,5 m
Digital communication wire
0,35 mm
2
3,5 m
C.T. connection cable
1,5 mm
2
3,5 m
TC input
0,8 mm
2
compensated 5
m
Pt100 input
1 mm
2
3 m
EMC conformity has been tested with the following connections
J, K, R, S, T, B, E, N (IEC 584-1, CEI EN 60584-1,
60584-2) L GOST, U, G, D, C
custom linearization is available
Triac output
20...240Vac ±10%, 1A max
Snubberless, inductive and resistive load I
2
t = 128A
2
s
Baud rate
1200, 2400, 4800, 9600, 19200
Environmental conditions of use
for internal use only, altitude up to 2000m