GH10TA USER MANUAL
PAGE
6
Issue I
July 2017
3.
TECHNICAL DATA
Power supply
230V
AC +10% -15%
NTC sensor resistance
characteristics
Operating temperature range
+5
°
C to +40
°
C
Humidity
20% to 80% RH
Temperature
Resistance
Fan protection
3.15A
0
7174.89
Sensor type
NTC 2.2kΩ
10
4374.83
Sensor operating temperature
0
°
C÷100
°
C
20
2747.10
30
1774.91
40
1172.09
Output
Maximum continuous
load
50
795.08
60
547.95
HUW pump / mixing pump
1A
200W
70
384.62
CH pump
1A
200W
80
275.86
Fuel feeder*
2A
400W
90
202.37
Fan *
1A
200W
100
149.16
*When a contactor or relay proxy is connected, use a dedicated
blowout system (eg varistor).
Omission of this security measure may
result in malfunction or damage to the controller output.
4.
ELECTRICAL SYSTEM AND CONNECTION RULES
1.
The boiler room should be equipped with a 230V/50Hz electrical system, according to the
applicable regulations.
2.
The electrical system (regardless of its type) should be terminated with a connection outlet fitted
with a protective terminal.
Use of an outlet without a protective terminal causes electrical shock
hazard!!!
3.
Connect the Controller to a separately installed power line protected with a properly selected
quick circuit-breaker or a residual-current device (RCD breaker).
Do not connect any other devices
to this line!!!
THE CONTROLLER IS POWERED FROM 230V/50HZ MAINS
ANY REPAIRS MAY BE CARRIED OUT ONLY WITH POWER SUPPLY
CUT OFF AT THE FUSE