GH10TA SERVICE MANUAL
STRONA
14
7.
USER SETTINGS
7.1.
Boiler Temperature Setting (U0)
You can change the boiler temperature setting using the following procedure:
7.2.
Feeder Standstill Duration (U1)
This is the period of time between two consecutive fuel feeds in the AUTO mode.
Settings are within the range from 5s to 250s.
You can change the setting using the following procedure:
STEP 1
STEP 2
STEP 3
STEP 4
→
→
or
→
Green LED lights on
the key.
Display shows the U0
setting value.
Move to
the U1
setting.
Set the desired value.
Save the new
setting.
Move to the U2
setting.
7.3.
Maintain Period (U2)
This is the period of time after which the Controller activates the feeder and fan for the period set by
the manufacturer for the MAINTAIN mode to prevent burning out of the boiler. Settings range is from 5
min. to 250 min. You can modify this setting in a similar way to the described in sections
7
.1 and
7.2
.
STEP 1
STEP 2
STEP 3
→
or
→
Green LED lights on the
key.
Display shows current
temperature setting.
Set a new desired
temperature within range
permitted by the boiler
manufacturer.
Save the new
temperature setting.
Move to the U1 setting
If during setting the new temperature
none of the following keys
,
,
is pressed for 15 s, the new temperature will not be saved
and the Controller will exit the programming mode.