Gebwell Qi Installation, operation, and maintenance manual
47
NOTE!
If the soft starter function is
Reboot 5min from
disorder
, do not reset the alarm of the heat pump. This will
cause a new malfunction and the compressor will not start.
Soft starter
Number of
flashes, red
LED
Failure
Operation
2
Incorrect phase sequence
Changing the phase sequence
3
Incorrect voltage
Automatic restart 5 min after the failure
4
Incorrect frequency
Automatic restart 5 min after the failure
5
Rotor is not spinning
Automatic restart 5 min after the failure
6
Start time > 1 s
Automatic restart 5 min after the failure
7
Overheating
Automatic restart 5 min after the failure
8
Over current after start-up
Automatic restart 5 min after the failure
9
Asymmetrical input voltage
Automatic restart 5 min after the failure, if all phases are connected