GEA Searle JG Installation And Maintenance Instructions Manual Download Page 2

Evacuation

To avoid potential moisture related problems, it is neces-
sary to evacuate the complete system to a minimum of 
1 torr (1.3mbar).  All parts of the system must be above 
freezing and ideally higher than +10°C during evacua-
tion.  

Electrical

All motors are single phase with automatic internal over-
load  protection,  and  can  be  operated  in  conjunction 
with a high quality ‘triac’ type speed controller. 
Generally ‘cage clamp’ type terminals are used.  These 
are  opened  by  inserting  a  correctly  sized  screwdriver 
into the square aperture adjacent to the conductor en-
try. 

Low temperature models

Defrost

The electric defrost option is supplied in kit form.  The 
kit consists of a heater element, securing clip(s) (except 
JG1) and a terminal block for electrical connection.  To fit 
the heater element, first remove the fan plate and inner 
drain tray.  The elements should be located as shown 
using  the  clips  provided,  (Diag  1)  and  the  inner  drain 
tray refitted.
The terminal blocks provided with the defrost kit should 
be clipped onto the DIN rail inside the junction box.  En-
sure that the cable is routed via the cable tie used for the 
earth lead and that all cables are secured clear of the 
fan(s) when the fan plate is repositioned.
If the initiation of defrost periods is by a timing device 
then it is recommended that it be initially set to four de-
frost periods per 24 hours until operating experience is 
gained. 
System  ‘pump  down’  (fans  running)  is  recommended 
(essential on very low temperature applications) prior to 
defrost so that the resulting defrost is neither prolonged 
nor uneven.
Drain line heater cables or tapes should be permanently 
energised and cover the drain pan connection.

Initial Defrost Termination Settings

Time/Time defrost system
 

Electric defrost:  30 minutes 

Time/Temperature termination system
 

Electric defrost minimum setting:  4.4°C

Time/Pressure termination system
 

Reverse cycle/hot gas defrost

 

Pressure equivalent to 25°C SST of the system  

 

refrigerant.  

 

Time: 10 min

 

Drain Down Time

A ‘drain down’ time, with fans off and no cooling, of five 
minutes duration should be given immediately following 
a defrost termination.  

Fan Delay Setting

a) 

With Thermostat: -7°C

b) 

With Pressure Switch: Refrigerant pressure at a  

 

saturation temperature of -12°C

3. 

INITIAL STARTING

Before running the unit for the first time, check that all 
guards, motor mountings and electrical covers are se-
cure, all unnecessary terminal block links are removed, 
internal wiring is clear of fans and that the fans rotate 
freely.  
After allowing the unit to operate at conditions close to 
design, the TEV must be adjusted to provide the correct 
level of superheat. This is between 0.6 and 0.75 x cooler 
TD,  to  a  maximum  of  8K.    Similarly  review  all  defrost 
settings.

4. 

MAINTENANCE (Routine)

WARNING!

UNIT  MUST  BE  ELECTRICALLY  ISOLATED 

BEFORE MAINTENANCE WORK IS UNDER-

TAKEN.

The following routine maintenance is required:
Periodically inspect units for ice build up where the 
ambient temperature is below 5°C.

Every 12 months check
Security of fixings especially fan motor mountings.
Refrigerant pipeline for damage and leaks.
Motor(s) rotate freely.
Electrical connections for security of attachment.
Defrost, if used, is operating effectively.

When necessary

Clean  the  fins,  guard,  drain  pan  and  drain  lines  and   
general  casework.  Care  must  be  taken  when  clean-
ing the fins to prevent damage.  A soft brush and mild       
detergent solution is recommended.

5. 

INVALIDATION OF GUARANTEE

Failure to install, set up or put to work any part of the 
equipment  in  the  manner  specified  in  the    Installation 
and   Maintenance   Instructions   could   invalidate  the 
guarantees    set   out   in   the   Standard   Terms   and  
Conditions of Sale.

2

Summary of Contents for Searle JG

Page 1: ... Location The location of the unit should be carefully selected to ensure that a Air distribution is not adversely affected by obstructions Product loading must be in accordance with good refrigeration practice b Air entering the unit is not obstructed c Good air distribution is achieved within the cooled space d The unit must be installed level in both directions To assist with the installation o...

Page 2: ...ost system Electric defrost 30 minutes Time Temperature termination system Electric defrost minimum setting 4 4 C Time Pressure termination system Reverse cycle hot gas defrost Pressure equivalent to 25 C SST of the system refrigerant Time 10 min Drain Down Time A drain down time with fans off and no cooling of five minutes duration should be given immediately following a defrost termination Fan D...

Page 3: ...nètre l appareil ne soit obstrué d aucune façon c Une bonne circulation d air soit assurée dans l espace à refroidir d L appareil soit installé horizontalement dans les deux directions Pour faciliter le montage de l appareil un plan d emplacement des fixations est imprimé sur l emballage Pour limiter le poids lors du montage et faciliter l accès aux fixations de l appareil la tôle de ventilation p...

Page 4: ... de dégivrage Minimum 4 4 C Durée Pression de fin de dégivrage Inversion de cycle dégivrage gaz chauds Pression équivalent à 25 C saturé du réfrigérant Durée 10 minutes Durée d écoulement d eau Un temps d écoulement de l eau de dégivrage avec ventila teurs arrêtés et pas d enclenchement du froid d une durée de 5 minutes doit être programmé après la fin de dégivrage Retard ventilation a par thermos...

Page 5: ...ß guter Kühlpraxis entsprechend erfolgen b der Lufteintritt in das Gerät nicht behindert wird c gute Luftverteilung im Kühlraum erzielt wird d das Gerät in beiden Richtungen waagerecht installiert wird Um die Montage zu erleichtern liegt der Verpackung eine Montageschablone bei Als weitere Hilfe können Sie den Ven tilator entfernen Das Gerät hat dann ein geringeres Gewicht und ist leichter zu hand...

Page 6: ...chließend nach der Abtauung erfolgen Verzögerter Ventilatoranlauf a mit Thermostat feste Einstellung 7 C b mit Druckschalter entsprechend dem Kältemittel druck bei einer Sättigungstemperatur von 12 C 3 ERSTER PROBELAUF Vor erster Inbetriebnahme ist zu kontrollieren daß alle Schut zgitter Motoren Befestigungen und elektrische Anschlüsse fest angezogen sind und die Ventilatorflügel frei drehen Es mu...

Page 7: ...age pour JG7 8 Abtau Kit JG7 8 JG7 8 E1 1 1 Fan motor assembly Ventilateur Ventilator Motor 231 920 028 1 1 1 1 2 2 3 3 Fan guard Grille de ventilateur Ventilator Schutzgitter 244 116 001 1 1 1 1 2 2 3 3 Drain connection 3 4 BSP Raccord d écoulement 3 4 BSP Tauwasser Anschluß 3 4 261 763 006 1 1 1 1 1 1 1 1 Gasket for drain connection Joint pour raccord d écoulement Dichtung für Tauwasser Anschluß...

Page 8: ...ß Zoll Refrigeration Connections Raccordements frigorifiques Kältemittel Anschlüsse Model Modèle Modell JG No of Fans Nbre de vent Anzahl Ventilatoren Approx Dry Weight kg Masse à vide kg Montagegewicht ca kg Dimensions Dimensions Abmessungen JG 7 8 JG 1 2 JG 3 4 JG 5 6 Part Number 272 000 009 ISSUE JUL98 01 GEA Refrigeration GEA Searle Ltd 20 Davis Way Newgate Lane Fareham PO14 1AR Tel 44 0 1329 ...

Reviews: