OPERATING INSTRUCTIONS 

 

GRASSO SYSTEM CONTROL 

FOR TWO STAGE CHILLER/ PACKAGES WITH SCREW 

COMPRESSORS 

 

 

_805011_om_gsc_sp2_gbr_1_.doc 

 15  

Number 

Title  

Help text 

50 Configuration 

Enter: 

 

Refrigerants 

 

SC-Type 

 

Code 

 

- with/ without economiser 

 

- scaling of the sensors 

 

90 

Main system menu 

To get to these menus, position the cursor on the menu name (using the 

 or 

 key) and confirm with the 

 key. 

Danger! 

Parameter changes in menu 20, 30, 35, 50 can cause serious damage to the screw compressor 
unit or chiller! 

 

1.2.4 Status displays 

[Chapter 1.3. in User Manual]

 

To get to the "status display" views, press the 

 key several times, or press the 

 key and then 

This display shows all of the information shown in the first actual values screen plus the status of the compressor 
unit. 

 

fig. 4: 

"Status messages" display 

AV-LP: 

Actual value (pressure or temperature) always displayed in °C 

SP: 

Set Point display in °C  

Pos LP: 

Current slide position in % 

dPoil: 

Differential oil pressure in bar 

Tc: 

Condensation temperature in °C 

dOilf: 

Differential oil filter pressure in bar 

 

 

Hint! 

See menu 05 actual values 

 

Summary of Contents for Grasso

Page 1: ..._805011_om_gsc_sp2_gbr_1_ doc 1 Grasso System Control for two stage Chiller Packages with Screw Compressors Operating Instructions...

Page 2: ...tion may be copied or published by means of printing photocopying microfilm or otherwise without prior written consent of Grasso This restriction also applies to the corresponding drawings and diagram...

Page 3: ...SORS _805011_om_gsc_sp2_gbr_1_ doc 3 SYMBOLS USED IN THIS MANUAL Danger This is an important warning Non observance these warnings can cause accidents with relevant damages on persons or serious damag...

Page 4: ......

Page 5: ...cription of the Grasso System Control 8 1 2 1 View 8 1 2 2 Lamps Push buttons 10 1 2 3 Operator terminal 11 1 2 3 1 Key assignment 12 1 2 3 2 Call up table of contents 14 1 2 4 Status displays 15 1 3...

Page 6: ......

Page 7: ...ACKAGES WITH SCREW COMPRESSORS _805011_om_gsc_sp2_gbr_1_ doc 7 TABLE OF FIGURES fig 1 View of outside of switchgear cabinet 8 fig 2 View of inside of switchgear cabinet 9 fig 3 GSC operator terminal 1...

Page 8: ...st important information for the operator The indexes are not identical with those of the GSC User Manual The index X X X under the headings of this operating instruction refers to the matching chapte...

Page 9: ...TWO STAGE CHILLER PACKAGES WITH SCREW COMPRESSORS _805011_om_gsc_sp2_gbr_1_ doc 9 fig 2 View of inside of switchgear cabinet 1 Profibus DP DP coppler 2 Bus Terminal 3 Type of Power Supply 4 Emergency...

Page 10: ...essor drive motor is switched off Yellow indicator light Warning This lamp flashes if an operating condition reaches a preset value Warning Pre alarm Detection of this warning can be acknowledged at t...

Page 11: ...apter 1 2 in user manual The operator terminal is the interface between the operator and the control unit All switching operating and control actions are carried out via this operator terminal fig 3 G...

Page 12: ...apacity control only Start LP compressor Press key for 5 sec in operation mode Manual Increase capacity of LP compressor in case of manual capacity control only without function Call up display of act...

Page 13: ...e and warning Confirm input Press the button once for display of a help text Switch over to the 2nd keyboard level Cursor keys Functions of the F1 F4 buttons These functions are only available if the...

Page 14: ...e to the Date Time menu 1 2 3 2 Call up table of contents Chapter 1 2 3 in user manual key A list of the available menus is then displayed To get to the table of contents press the Number Title Help t...

Page 15: ...ause serious damage to the screw compressor unit or chiller 1 2 4 Status displays Chapter 1 3 in User Manual To get to the status display views press the key several times or press the key and then Th...

Page 16: ...eted Running Compressor motor running in Delta or startup has been completed Package Chiller in operation Psuc Limitation A capacity limitation is active suction pressure too low reduce output solenoi...

Page 17: ...g LP Text display flashes Italic lettering Text appears as static text Normal lettering The overall status of the compressor unit is displayed with the LEDs in and Key Colour Status Explanation Green...

Page 18: ...hile MAINS ON Peripheral error in the internal peripheral functions Further information about the malfunction that has occured can be read out of the diagnosis memory using the PG BATF red Battery err...

Page 19: ...4th row the status message is shown By scrolling with the cursor keys and all active alarms and warnings are displayed 1 4 2 No alarm signal and the compressor will not start Chapter 6 5 in user manu...

Page 20: ...HILLER PACKAGES WITH SCREW COMPRESSORS 20 _805011_om_gsc_sp2_gbr_1_ doc 1 4 3 Restart following Alarms Chapter 7 2 in user manual fig 5 Restart following Alarms Caution It is not possible to restart t...

Page 21: ...w press the key or in the case that several alarms have occurred simultaneously Step Procedure 1 Call up the Alarms menu by pressing the key 2 Select the View menu item for the alarms by pressing the...

Page 22: ......

Reviews: