background image

Auxiliary 

Additional controls are located
behind the room cabinet.

To remove the room cabinet,
see page 5.

VENT

OPEN

 Control

— TEMP OVERRIDE —

SETBACK 

 

FAN

CYCLE 

 

– 

HEATING 

NORMAL 

 MAXIMUM 

 

TL2 TL1

‘EAT 

TL2 TL1

 

\

Unit 

 

This 

knob 

 set 

 CLOSE at the

This switch   set at 

ON at 

factory. When it is in this position,

factory to allow the air conditioner

the vent door is closed and only
indoor air is filtered, cooled or
heated and circulated by the air
conditioner.

Switching the knob to OPEN opens
the vent door to allow some outside
air to enter the room. However,

cooling or heating effectiveness is
reduced when the control is set at
OPEN, so we suggest you don’t
keep it there long.

If the knob is not set all the way in
CLOSE position, the vent light will
remain on.

to operate in the cool, heat or fan
only modes and the Freeze Sentinel,
Heating Economy Switch and Temp
Override to operate if it is needed.

If this switch is set at OFF, the air
conditioner will not operate in 
mode 

 the Freeze Sentinel,

Heating 

 Switch 

Temp Override 

 not function.

Caution: The Unit Power Switch
is not a power disconnect.  
If 
power must be disconnected from
the unit, remove the line cord plug
from the wall outlet, or remove the
fuses, or turn off the circuit
breakers at the power panel.

4

‘Fan Cycle 

This switch is set at 

 at the

factory to provide continuous fan
operation in cool or heat modes. If
you want the fan to cycle on and off
with the compressor or resistance

\

heater, set the switch at 

 

 

Heating 

 

For maximum heating economy,
this switch is set at MAXIMUM
at the factory. Until the outside air
temperature drops to 

 the heat

pump is the primary source of heat.
At 

 and below, full resistance

heat takes over.

Set this switch at NORMAL and

the change from heat pump to
resistance heating occurs when
the outside air temperature 
to 

Temp Limit 

The TEMP LIMIT switch is used
to adjust the thermostat range. Set
it to limit the lowest temperature

that can be obtained on cooling and
the highest temperature that 

 

obtained on heating.

COOL and HEAT settings range
from NORMAL to 

 Both

controls are set at NORMAL at
the factory.

 

 Mines

Heating

Normal

57- 

90°

57- 90°

TL1

71- 

90°

57- 77°

TL2

77- 

90°

57- 73°

TL3

83- 91°

57- 68°

Summary of Contents for Zoneline 4000 Series

Page 1: ... Switch 4 Freeze Sentinel 3 Heating Economy Switch 4 Indicator Lights 3 Master Controls 3 Model and Serial Numbers 2 Problem Solver 6 Repair Service 7 Room Cabinet and Case 5 Safety Instructions 2 Thermostat Control 3 Unit Power Switch 4 Ventilation Control 4 Warranty Back Cover GE W m mm Heat Pump hneline Models 4000 Seties 5000 Seties ...

Page 2: ...ribed in this Use and Care Book This air conditioner must be properly installed in accordance th the Insolation Instructions before it is used Never use an extension cord th this apptiance SAW THWE STRUCTIONS Energy Saving Tips Keep the air filter clean See instructions on page 5 For most efficient operation keep vent in closed position except when you want to let outside air enter the room Don t ...

Page 3: ...ode ON STOP opERAT oN m COOL FEAT HIGH LOW 1 AUTO ANSPEED B Master Controls Push the Operation Button once to turn the air conditioner on push again to turn it off If the unit does not operate when you push this button to start it check to see if the Unit Power Switch located behind the room cabinet is on See page 4 Slide the Selector Switch to COOL for cooling or to HEAT for heating Slide the Fan...

Page 4: ...ting Uonomy Switch and Temp Override will not function Caution The Unit Power Switch is not a power disconnect If all power must be disconnected from the unit remove the line cord plug from the wall outlet or remove the fuses or turn off the circuit breakers at the power panel 4 Fan Cycle Switih This switch is set at CONT at the factory to provide continuous fan operation in cool or heat modes If ...

Page 5: ...soiled they may need to be professionally steam cleaned a service available through your GE service outlet Air Miter The air filter behind the room cabinet should be washed at least every W days or as often as it needs cleaning Access to the filter is obtained by removing the room cabinet Case F L p i Iw d Room Cabinet To remove the air filter grasp the pull tabs on the front of th fil er as shown...

Page 6: ...r registers and cold air returns o entl ation Control maybe set at p position allowing outside air to enter the room Q The Temperature Limit Switches may be sgt at a setting other than normal This will limit the operating ranges See page 4 Position of the louvers will affect temperature See page 3 BURNING ODOR Dust accumulating on surface of heating e ement during tmnspo tion or storage AT START O...

Page 7: ...rther help FIRST contact the people who serviced your appliance Explain why you are not pleased In most cases this will solve the problem NEXT if you are still not pleased write all the details including your phone number to Manager Consumer Relations GE Appliances Appliance Park Louisville Kentucky 40225 FINALLY if your problem is still not resolved write Major Appliance Consumer Action Panel 20 ...

Page 8: ... IS N COVERED Service trips to teach you how to Improper installation Failure of the product resulting from use the product If you have an installation modifications to the product or due to Read your Use and Care material problem or if the air conditioner unreasonable use including failure to If you then have any questions is of improper cooling or heating provide reasonable and necessary about o...

Reviews: