background image

20

Before you call for service…

Consumer Support

Tr

oubleshooting T

ips

Care and Cleaning

Operating Instructions

Safety Instructions

Troubleshooting Tips 
Save time and money! Review the charts on the following
pages first and you may not need to call for service.

Problem

Possible Causes

What To Do

Zoneline does

The unit is 

Make sure the Zoneline plug is pushed completely 

not start

unplugged.

into the outlet.

The power cord is not

Remove the room cabinet and make sure that the 

firmly attached.

yellow connector on the end of the power cord is 
firmly engaged.

The fuse is blown/circuit

Check the house fuse/circuit breaker box and replace

breaker is tripped.

the fuse or reset the breaker.

The unit is waiting for

This is normal. The Zoneline will start again after 

the compressor overload

it resets.

protector to reset.

Power failure.

If power failure occurs, set the mode control to 

STOP.

When power is restored, set the mode control to the 
desired setting.

There is a protective time delay (up to 3 minutes) to 
prevent tripping of the compressor overload. For this 
reason, the unit may not start normal heating or cooling 
for 3 minutes after it is turned back on.

The current interrupter 

Press the 

RESET

button located on the power cord plug 

device is tripped.

or the box near the plug.

If the 

RESET

button will not stay engaged, discontinue use 

of the Zoneline and contact a qualified service technician.

Zoneline does not cool

Indoor airflow 

Make sure there are no curtains, blinds or furniture

or heat as it should

is restricted.

blocking the front of the Zoneline.

Outdoor airflow is

Make sure the rear grille is not restricted. This can 

restricted or recirculated.

cause the unit to cycle off due to the compressor 
overload protector.

Outdoor grille must have a minimum of 65% free area. 
Non-GE grilles may be too restrictive for proper 
performance. Consult your salesperson for assistance.

The temp control may

Turn the control to a lower or higher setting.

not be set properly.

NOTE: 

The temperature limiter may be limiting the temperature range.

The air filter is dirty.

Clean the filter at least every 30 days.
See the 

Operating Instructions

section.

The room may have 

When the Zoneline is first turned on you need to

been hot or cold.

allow time for the room to cool down or warm up.

Outdoor air is 

Set the vent control to the closed position.

entering the room.

Burning odor at the start

Dust is on the surface 

This can cause a “burning” odor at the beginning of

of heating operation

of the heating element.

the heating operation. This odor should quickly fade.

Summary of Contents for Zoneline 2900

Page 1: ...ort Consumer Support Back Cover Warranty 23 Heat Cool Model 2900 Heat Pump Model 3900 Owner s Manual and Installation Instructions ge com Write the model and serial numbers here Model ________________...

Page 2: ...ck of this manual Replace immediately all electric service cords that have become frayed or otherwise damaged A damaged power supply cord must be replaced with a new power supply cord obtained from th...

Page 3: ...o set the air conditioner to run for 8 hours before it automatically returns to the previous setting When in the cooling mode and the sleep timer is set the set temperature will automatically increase...

Page 4: ...t be removed from the vent door before use See the Installation Instructions in the back of this manual Air Direction To adjust the air direction remove the room cabinet Remove the 7 louver screws tha...

Page 5: ...es models only Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support All Electric Heat This electric heat option functions only on the 3900 Series models W...

Page 6: ...e limiting is controlled by the second six auxiliary switches The first three switches are used to select the cooling limits and the remaining three switches are used to control the heating limits Thi...

Page 7: ...an auxiliary switch for AZ2900 models and must remain in the DOWN position BOOST Heat Boost Operation Auxiliary Controls Terminal Connections The auxiliary controls are located behind the room cabine...

Page 8: ...t When connected the unit will be controlled by a remote thermostat NOTE The number 4 dip switch must be in the enabled UP position to activate the remote thermostat See the installation instructions...

Page 9: ...ent filter tab and pull the filter out by sliding it to the right To clean the vent filter Run water through the filter from the back side Dry thoroughly before replacing Outdoor Coils The coils on th...

Page 10: ...rough the filters from the back side Dry thoroughly before replacing NOTE The air filters are interchangeable and will fit in either the right or left side To remove the air filters To replace the air...

Page 11: ...or local codes and ordinances For personal safety this Zoneline must be properly grounded Protective devices fuses or circuit breakers acceptable for Zoneline installations are specified on the namep...

Page 12: ...at were not designed for your new GE Zonelines The RAK40 contains air deflectors and gaskets that mount to the unit to direct the hot exhaust air away from the air intake to allow the unit to function...

Page 13: ...ler to ensure the connection of components is done in accordance with these instructions and all electrical codes Branch Circuit and Proper GE Unit Amperage Rating Subbase Kit 15 RAK204D15P 20 RAK204D...

Page 14: ...e for direct connection The instructions provided with the selected subbase kit must be carefully followed It is the responsibility of the installer to ensure the connection of components is done in a...

Page 15: ...to attach conduit coming from the branch circuit Remove the knockout attach the conduit and bring wires into the junction box Leave 6 of wire free at the end of the conduit to allow connections to be...

Page 16: ...r 5 00 4 10 KW 230 208 Volt Heater Wattage Power Supply Kits 230 208 Volts Circuit Protective Device RAK4157 2 55 KW 2 09 KW 15 Amp Time Delay Fuse or Breaker RAK4207 3 45 KW 2 82 KW 20 Amp Time Delay...

Page 17: ...ies wall cases are insulated Insulation kit RAK901L is available for use with RAB77 or existing uninsulated wall cases when needed NOTE For installation with a subbase or duct adapter see the instruct...

Page 18: ...e top over the rail along the unit top 1 then pushing it in at the bottom 2 4 Installation Instructions 18 NOTE There are several extra holes in the unit side flanges for installation in wall cases ot...

Page 19: ...g onto external building walls we recommend the use of RAD10 Drain Kit External Drain See the Installation Instructions in the RAD10 kit Internal Drain See the Installation Instructions in the RAD10 k...

Page 20: ...rrupter Press the RESET button located on the power cord plug device is tripped or the box near the plug If the RESET button will not stay engaged discontinue use of the Zoneline and contact a qualifi...

Page 21: ...off the warm enough during produces air that feels heat pump and warms with electric heat only heating operation cooler than desired NOTE Use of this option will result in increased energy consumption...

Page 22: ...o hear a fan noise stop and start You may notice a few minutes delay in starting if you try to restart the Zoneline too soon after turning it off or if you adjust the thermostat right after the compre...

Page 23: ...s to the product or due to unreasonable use including failure to provide reasonable and necessary maintenance Failure or damage resulting from corrosion due to installation in a coastal environment ex...

Page 24: ...call 800 TDD GEAC 800 833 4322 Parts and Accessories ge com Individuals qualified to service their own appliances can have parts or accessories sent directly to their homes VISA MasterCard and Discov...

Reviews: