background image

GE Power Controls

PCST-3303E-R0

VAT2000 AC Drive Series

U2KV23PI0

Parallel Interface

INSTRUCTION MANUAL

NOTICE

1.  Read both this manual and VAT2000 Instruction

Manual (PCST-3251) before using the
U2KV23PI0, and store in a safe place for
reference.

2.  Observe the warnings, cautions and other matters

described in this manual.

3.  Make sure that this manual is delivered to the final

user.

GE Power Controls

Summary of Contents for U2KV23PI0

Page 1: ... MANUAL NOTICE 1 Read both this manual and VAT2000 Instruction Manual PCST 3251 before using the U2KV23PI0 and store in a safe place for reference 2 Observe the warnings cautions and other matters described in this manual 3 Make sure that this manual is delivered to the final user GE Power Controls ...

Page 2: ... Connection and setting procedure 4 3 2 Data input mode selection and signal specifications 5 3 3 Signal logic and circuit format selection 7 4 Usage of PSO Terminal Function 8 Appendix Table 1 CN1 pin layout 9 Appendix Table 2 TB1 terminal functions 9 Appendix Table 3 Hardware Option Function Setting 10 ...

Page 3: ...nchronous method with strobe signal or asynchronous method with sample Data width Select from 16 bit non multiplexed or 8 bit multiplexed Circuit voltage current 24VDC 5mA tolerable leakage current 0 5mA Interface power 24V 10 0 2A or higher capacity to be provided by the user Open collector output section No of points 2 points PSO4 5 Max voltage current 30VDC 50mA Control PCB Parallel data input ...

Page 4: ... terminals L 1 or L 2 and L is 15V or less before starting the inspections Check with the CHARGE LED if the unit is not provided with the L terminal 2 If the other option PCB is installed onto the position for option II on the control PCB cover install this PCB onto the position for option III Refer to Fig 2 1 3 When wiring to TB1 use AWG26 to 16 0 14 to 1 5mm 2 for the wires Wires should be termi...

Page 5: ...over Option III Control PCB cover Option I Option II The mounting position of V23 PI0 Fig 2 1 Installation of optional PCB NPSF ST19 0 1 M EID EN N62P30449 1 5A MADE IN JAPAN TB1 1 25 26 2 SOURCE SINK 1 W 1 2 CP1 1 2 CN1 Fig 2 2 Optional PCB ...

Page 6: ...able connection hole In this case the protective structure will be IP00 CN1 25 1 26 2 Max 30m 26 core flat cable Sequencer or digital switch W1 1 2 Parallel data input short pin TB1 1 2 24V power supply EX0 EX24 Note The 24V power supply is to be provided by the user Fig 3 1 Connection of parallel data input section 2 Setting procedure 1 Decide the circuit format and data format 2 Decide the circu...

Page 7: ...with the rising edge of the strobe STB D 0 D 1 5 S T B O F F O N Data 0 Data 1 Data 2 ts th tcy Data 0 Data 1 tw tds Internal data Fig 3 2 16 bit with strobe time chart 2 8 bit multiplexed with strobe C32 0 2 The 16 bit data is divided into the low order 8 bit and high order 8 bit with the LSB signal and each is loaded with the rising edge of the strobe STB D 0 D 7 S T B O F F O N Data 0 high orde...

Page 8: ...a 1 Data 2 Data 3 1 2 3 4 1 2 3 4 1 2 1 2 1 tsp Note Data 2 and 3 are not loaded in this case Fig 3 4 Sample mode time chart 4 Timing specifications Table 3 1 Symbol Name Specifications t cy Cycle time 25mS t w STB pulse width 3mS t s Data setup time 2mS t h Data hold time 2mS t ds Strobe delay 15 25mS t da Sample mode delay 50 60mS t sp Internal sample time 10 2mS ...

Page 9: ...ter No C32 1 Appendix Table 3 2 Signal common selection W1 Setting of all signal commons to EX0 or EX24 can be selected with the W1 setting The sequence output method open collector and open emitter can both be corresponded to with this V 2 3 P I 0 W1 E X 0 E X 2 4 1 2 D 0 D 1 5 T B 1 2 T B 1 1 S T B L S B Controller such as sequencer Open collector output Open emitter output External 24V power su...

Page 10: ... for details on the sequence output signal functions Table 4 1 PSO terminal settings Sequence output signal default values Terminal Parameter No setting data output signal PSO4A PSO4B PSO4C C33 0 5 LCL PSO5A PSO5B PSO5C C33 1 6 REV The sequence output PSO4 5 terminals are laid out in CN1 Appendix Table 1 C N 1 2 1 C N 1 2 4 C N 1 2 5 2 6 Load max 50mA max 30V P S O 4 P S O 5 V 2 3 P I 0 C N 1 2 2 ...

Page 11: ...X24 External 24V power supply input for the parallel data input 20 EX0 External 24V power supply input common for the parallel data input CN1 21 PSO4 PSO4 output terminal open collector 22 COM1 23 COM1 PSO output terminal common 24 PSO5 PSO5 output terminal open collector 25 COM1 26 COM1 PSO output terminal common CN1 25 1 26 2 View from connector insertion side 1 Appendix Table 2 TB1 terminal fun...

Page 12: ...ne time constant input points selection 2 1 3 1 Serial fixed 2 Panel fixed 3 Sequence O O Block C parameters H W option function constants list Application No Parameter Unit Default Min Max Function ST V f VEC PM C32 PC parallel Interface 0 Input mode strobe 1 1 3 1 16 bit strobe 2 8 bit time multiplexed strobe 3 16 bit sample O 1 Input mode input logic 1 1 2 1 1 at closed circuit 2 1 at opened ci...

Page 13: ...t parameters 6 0 24 Set this when the relay interface option U2KV23RY0 and Parallel interface option U2KV23PI0 are mounted Refer to Instruction Manual PCST 3301 for other details O Value Output signal Value Output signal Value Output signal Value Output signal 0 RUN 8 ATN 16 ACC 24 ULMT 1 FLT 9 SPD1 17 DCC 2 MC 10 SPD2 18 AUXDV 3 RDY1 11 COP 19 ALM 4 RDY2 12 EC0 20 FAN 5 LCL 13 EC1 21 ASW 6 REV 14...