GE Oil & Gas
ES-761 Rev F
Page 9 of 12
Copyright 2015 as an unpublished trade secret. This document and all information herein is the property of Dresser Flow
Technologies, Dresser Inc. It is confidential and must not be made public or copied and is subject to return upon demand.
6.2 Model SVi1000abc, where a = PR Installation
NON-HAZARDOUS LOCATION – UNSPECIFIED EXCEPT
THAT BARRIERS MUST NOT BE SUPPLIED FROM NOR
CONTAIN UNDER NORMAL OR ABNORMAL CONDITIONS A
SOURCE OF POTENTIAL WITH RESPECT TO EARTH IN
EXCESS OF 250 VOLTS RMS OR 250 VOLTS DC
1
2
3
4
Optional Hand Held
Communicator
(see 7.6)
HAZARDOUS LOCATION
SEE NOTES 7.1 AND 7.2
4-20mA IN
4-20mA
Out
1
2
3
4
SVi1000
Shunt Zener Diode Safety Barrier –
Controller Output Type (see sec 7.3)
Transmitter Safety Barrier Type with
internal or external Sense Resistor
(see sec 7.5)
24 VDC from DCS
4-20mA Set Point from DCS
Optional Hand Held
Communicator
(see 7.6)
Equi-Potential
SVi1000 abc equipped with
Position Retransmit
Terminal Board (a = PR)
Masoneilan SVi1000 Positioner Quick Start Guide
=
|
81
© 2016 General Electric Company. All rights reserved
.