Masoneilan SVi1000 Positioner Quick Start Guide
=
|
37
© 2016 General Electric Company. All rights reserved
.
2. Connect the 4 - 20 mA input signal and the optional switches or position
retransmit by:
a. Stripping the insulation at the end of both wires 0.43" / 11 mm.
b. Inserting the stripped end of the wires fully in to the appropriate terminal.
Loosen the terminal screw if required to insert the wire.
Refer to the label next to each screw terminal to determine the function of the
terminal and correct polarity (see Figure 19 for 4 - 20 mA connections and
Figure 20 on page
38 for position retransmit).
c. Tightening the terminal screws (to a torque of 5 to 7 lb·in).
Ground
4- 20 mA
Input Signal
Optional Solid
State Switches
Figure 19
Connections to Electronics Module with Switches (via Interface Board)