Physical and Operational Specifications
This section provides the physical and operational specifications for the SVi1000. Specifications
are subject to change without notice
Table 6: Environmental Specifications
Parameter
Storage & Transport (Packaged)
Operating Temperature Limits
-40 °F to 185 °F (-40 °C to 85 °C)
Storage Temperature Limits
-58 °F to 200 °F (-50 °C to 93 °C)
Temperature Effect
< 0.005% / °F typical; -40 °F to 180 °F (< 0.01% / °C typ-
ical; -40 °C to 82 °C)
Supply Pressure Effect
0.05% per psi (.73% per bar)
Operating Relative Humidity
5 to 100% non-condensing
Storage Relative Humidity
0 to 100% non-condensing
Humidity Effect
Less than 0.2% after 2 days at 104 °F (40 °C), 95% Rela-
tive Humidity.
Electromagnetic Compatibility
Electrostatic
IEC 61514 Industrial-Process Control systems - meth-
ods of evaluating the performance of intelligent valve
positioners with pneumatic outputs.
IEC 61326 Electrical equipment for measurement, con-
trol and laboratory use - EMC requirements.
Fast Transient Burst
No effect at 2 kV (Coupling clamp EN61000-4-4 or
IEC1000-4-4).
Vibration Influence
Measured at SVi1000 Housing
4 mm at 5 - 15 Hz - Negligible
2 G at 15 - 150 Hz Less than 2 % of span
1 G at 150 - 2000 Hz - Less than 2% of span
Appendix C.
Specifications,