DESCRIPTION

The ProSys Lighting Control System is a small network of
relay panels and occupant control switches linked by a 4-wire
dataline. Together, these devices form a reconfigurable
switching platform — one that uses “softwiring” instead of
hardwiring to link occupant switches to relays. Scheduling
capability can be readily added by simply mounting an
RCLK8PS Softwired Clock to the DIN rail in any relay panel.

The RINTERxxxxPS(P)

1

 is the interior for a 

ProSys

Lighting Control System

 Relay Panel.

 The complete relay

panel assembly will include the following:

1. Tub (RTUBxx)
2. Interior (RINTERxxxxPS or RINTERxxxxPSP)
3. Power Supply (RPWRxxx)
4. Cover (RCOVxxxx)

This instruction sheet will show you how to:

1. Install the Relay Panel(s)
2. Install and Test the Dataline
3. Document the Relay Panels

Full descriptions of the installation and operation of Softwired
Switches and the Softwired Clock and other optional
automation devices are located in other sections of this
manual and are provided with each hardware unit.

Before starting, read the following installation
instructions. If you have questions, call GE Total
Lighting Control Service at:

1-877-584-2685 (LTG-CNTL) in the USA and Canada.

RINTER2424PSP 24-Relay Interior shown with RTUB24

ProSys Lighting Control System
Catalog Number RINTERxxxPS(P)

GE Total Lighting Control

ProSys™ Lighting Control System Relay Panels

These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with
installation, operation or maintenance.  Should further information be desired or should particular problems arise that are not covered for the purchaser's purposes,
the matter should be referred to the GE Company.

Summary of Contents for ProSys DEH40212

Page 1: ... the Dataline 3 Document the Relay Panels Full descriptions of the installation and operation of Softwired Switches and the Softwired Clock and other optional automation devices are located in other sections of this manual and are provided with each hardware unit Before starting read the following installation instructions If you have questions call GE Total Lighting Control Service at 1 877 584 2...

Page 2: ...earance Pulling Wires Route line voltage wiring through the 21 2 knockouts in either the top or bottom of the tub Route Class 2 low voltage dataline from the remote switches or other controls through the 3 4 knockouts in either end Install Interior Power Supply Attach the power supply to the frame bottom of 12 relay interior and left side of 24 or 48 relay interiors and plug the low voltage connec...

Page 3: ... may be softwired to relays within the panel Channels are used to group relays for common control When a ProSys system includes an automation module RCLK8PS Softwired Clock we strongly recommend you turn to the installation instructions for that automation module and complete the documentation before softwiring any relays to channels However if automation is to be provided by an interface to anoth...

Page 4: ... panel address is set higher than 30 the channel LEDs in the panel will flash Setting the panel address to 30 or below will return the panel to normal operation If a panel is set to the same address as another panel then the two panels will not operate properly The ProSys LM panels can be setup in groups of 30 where the panels in a group can be numbered from 00 to 30 Note To ensure good communicat...

Page 5: ...uld be tested for continuity and isolation from ground To test for continuity remove the red and black dataline wires at panel 01 and wire nut together short the wires together Go to the last panel in the series and measure the resistance between the red and black terminals It should be less than 3 ohms Return to panel 01 and restore the red and black wires to their associated terminals For shorts...

Page 6: ...6 DEH40212 Installation Instructions GE Total Lighting Control 41 Woodford Avenue Plainville CT 06062 2000 General Electric Company GE Total Lighting Control DEH40212 BL 0700 R02 ...