DEH40212 Installation Instructions

The dataline connects the relay panels, switches and optional
control modules. Within the 4-wire dataline are two twisted
pairs: the red and black wires, carrying data; and the blue and
white wires, providing power to the dataline switches and
control modules.

For simplicity, we refer to a 4-wire dataline running between
a relay panel and the dataline switches as a “Local Dataline”.
The relay panel provides the low-voltage power to all of the
intelligent devices on that section of the dataline.

The dataline running between relay panels is known as the
“Global Dataline,” and it uses only the red and black data
wires. The blue and white wires are not connected and should
be trimmed.

Panel Addressing

The two rotary switches on each relay panel set its address,
allowing the differentiation between relays in different panels.

NOTE:

 The first panel address must be set at 01 and the others

numbered sequentially 02, 03, and so on, between 02 and 30 as
shown to the right. If the panel address is set higher than 30, the
channel LEDs in the panel will flash. Setting the panel address to 30
or below will return the panel to normal operation. If a panel is set to
the same address as another panel, then the two panels will not
operate properly. The ProSys LM panels can be setup in groups of 30
where the panels in a group can be numbered from 00 to 30.

Note: To ensure good communications between panels,
the installer must comply with the dataline specification.
GE will not warrant a system using a dataline that does
not meet our specification. To avoid questions, use GE
RLONWIRE-4P (plenum rated). Do not run the dataline
in conduit or wiring trays with power wires. Do not
connect the local datalines from two different panels.

DATALINE INSTALLATION

GE RLONWIREP-S4 Dataline Wire Specifications

• #18 AWG (7 strands x 26 AWG)
• 2 independent twisted pairs – black/red, blue/white
• Unshielded copper conductors
• 2 inch twist lay on pairs, 6 inch twist lay on cable
• Plenum-rated copolymer jacket, 0.230" O.D.
• FEP 0.010" insulation, 0.060" O.D.
• 30 pF/foot maximum capacitance
• -20°C to 150°C operating temperature range
• 17 lbs. per 500 foot reel
• UL rated

GLOBAL (PANEL-TO-PANEL) DATALINE

PANEL 01

PANEL 02

PANEL XX

Summary of Contents for ProSys DEH40212

Page 1: ... the Dataline 3 Document the Relay Panels Full descriptions of the installation and operation of Softwired Switches and the Softwired Clock and other optional automation devices are located in other sections of this manual and are provided with each hardware unit Before starting read the following installation instructions If you have questions call GE Total Lighting Control Service at 1 877 584 2...

Page 2: ...earance Pulling Wires Route line voltage wiring through the 21 2 knockouts in either the top or bottom of the tub Route Class 2 low voltage dataline from the remote switches or other controls through the 3 4 knockouts in either end Install Interior Power Supply Attach the power supply to the frame bottom of 12 relay interior and left side of 24 or 48 relay interiors and plug the low voltage connec...

Page 3: ... may be softwired to relays within the panel Channels are used to group relays for common control When a ProSys system includes an automation module RCLK8PS Softwired Clock we strongly recommend you turn to the installation instructions for that automation module and complete the documentation before softwiring any relays to channels However if automation is to be provided by an interface to anoth...

Page 4: ... panel address is set higher than 30 the channel LEDs in the panel will flash Setting the panel address to 30 or below will return the panel to normal operation If a panel is set to the same address as another panel then the two panels will not operate properly The ProSys LM panels can be setup in groups of 30 where the panels in a group can be numbered from 00 to 30 Note To ensure good communicat...

Page 5: ...uld be tested for continuity and isolation from ground To test for continuity remove the red and black dataline wires at panel 01 and wire nut together short the wires together Go to the last panel in the series and measure the resistance between the red and black terminals It should be less than 3 ohms Return to panel 01 and restore the red and black wires to their associated terminals For shorts...

Page 6: ...6 DEH40212 Installation Instructions GE Total Lighting Control 41 Woodford Avenue Plainville CT 06062 2000 General Electric Company GE Total Lighting Control DEH40212 BL 0700 R02 ...

Reviews: