background image

Power  Break® 

II 

Circuit  Breakers 

Draw-Out Breaker Installation 

:· 

.1. 

Racking  Tool 

Figure 

Wrench attached to the breaker racking shaft. 

Substructure 

Rejection 

Feature 

.06in 

minimum 

Breaker 

Rejection 

Feature 

Compartment 

Position Indicator 

Figure 

8. 

Compartment  position indicator on the front of  the breaker. 

Removing the  Breaker 

Use  the  following  procedure  to  remove  the  draw-out 

breaker from  the  substructure. 

CAUTION: 

The  breaker  must  be 

OFF 

before  it  is  dis­

connected  and removed. 

ATTENTION: 

Le  disjoncteur  doit  etre  en  position 

OFF 

avant  qu'il  ne soit debroche et depose. 

1. 

Engage  the 

!2 

-inch  square  end  of  the  racking 

shaft  with  the  supplied  wrench,  catalog  number 
TDORT, as  illustrated  in  Figure 

7, 

and  rotate  the 

shaft  counter-clockwise  to  withdraw  the  breaker  to 

the 

TEST 

or 

DISCONNECTED 

position.  The 

compartment  position  indicator  is  shown  i n  

Figure  8. 

2. 

Pull  the  substructure  rails  out  as  far  as  possible 

until  they  drop  into  the  horizontal  locked  posi­
tion,  as  illustrated  in  Figure 

9. 

3. 

From  the 

DISCONNECTED 

position,  pull  the 

breaker  out  on  the  rails  until  the  front  rollers  fall 
into  the  detent,  as  illustrated  in  Figure 

6. 

4. 

The  breaker  can  now  be  rotated  about  the  front 
roller  by  pulling  forward,  as  illustrated  in  Figure 

10,  for  inspection  of  the  rear  of the  breaker,  or  it 

can  be  completely  removed  after  attaching  the 

Lifting  Bar,  as  illustrated  in  Figures 

and 

5. 

Figure 

9. 

Withdrawing the substructure rails. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for Power Break II

Page 1: ...GEH 62718 Installation Instructions Power Break II Circuit Breakers Draw Out BOD 4000 Ampere Frames w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 2: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 3: ...ensure accuracy the information contained herein does not cover all details or variations in hardware and software nor does it provide for every possible contingency in connection with installation o...

Page 4: ...cutoff switch 2 4 Lifting Bar attached to a draw out breaker for manual lifting 3 5 Lifting Bar attached to a draw out breaker for lifting with a hoist 3 6 Breaker installed on rails ready to be pushe...

Page 5: ...the connected position fed through when the Secondary Disconnects Control power is provided through the secondary disconnects in the test and connected positions only All accessories terminate at dedi...

Page 6: ...208 SPHDOS08 SSD16X210 X216 SPSDOS16 SHD16X210 X216 SPHDOS16 SSD20X220 SPSDOS20 SHD20X220 SPHDOS20 SSD25X21 0 X220 X325 SPSDOS25 SHD25X210 X220 X325 SPHDOS25 SSD30X330 SPSDOS30 SHD30X330 SPHDOS30 SSD4...

Page 7: ...ment position indicator is shown in Figure 8 NOTE If the breaker does not fit the structure check the rejection relationship illustrated in Figure 8 to verify that a correctly rated breaker is being i...

Page 8: ...pplied wrench catalog number TDORT as illustrated in Figure 7 and rotate the shaft counter clockwise to withdraw the breaker to the TEST or DISCONNECTED position The compartment position indicator is...

Page 9: ...ressed air for blowing out equipment 2 Inspect buses and or terminal lug connections for signs of overheating or weakening of insulating supports Check indicating devices and mechanical and key interl...

Page 10: ...e equipment Lubrication All the areas subject to friction are liberally coated at the factory with Mobil 28 red grease If the contact surfaces the breaker power screw and the interlock pin are cleaned...

Page 11: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 12: ...GE Electrical Distribution Control General Electric Company 47 WoodfordAve Plainville CT 06062 GE 62718 0697 7997 General Electric Company w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: