Diagnostics
How to diagnose by LED Indicator
The following table lists the LED Color, Status and the action to be taken while
troubleshooting.
Table 48: LED Indicators
Color
Status
Action
All LED turns off
No power
Check main power Cable
System power is not
supplied.
Contact Sales team and
send module for repair.
MOD LED flashes
green
Failure of initialization of
EEPROM parameter.
Contact Sales team and
send module for repair.
MOD LED flashes
red
Excess of IO Modules
connected
Excess of IO size
Wrong IO composition
Occurrence of EEPROM
checksum error
Use IO Modules up to 32.
Compose that IO total size
is not excess.
Check composition I/O
Module
MOD LED is red
Wrong address ID
Occurrence of critical error
in firmware
Contact Sales team and
send module for repair.
I/O LED turns off
Failure of realization IO
Module
No IO Module connected
Check connector status
both RSTi series and IO
module.
I/O LED flashes
red
Failure of configuration baud rate
Check communication
cable with Master
Check power for master.
Failure of initialization I/O
Use IO Modules up to 32.
Compose that IO total size
is not excess.
RSTi series notice unidentified IO
module ID. Check status of IO
module.
I/O LED is red
Failure of exchanging I/O data
Check status of IO connection.
NET LED turns off Failure of communication with Master
Check main power for master and
communication cable.
NET LED flashed
green
Failure of exchanging data with
master
Check status in software for Master
configuration.
NET LED is red
Communication connecting lost
Check BUS line cable for
connection with master.
Check duplication address.
How to diagnose when device cannot communicate to network
■
Inspection of wrong or omission cable connection