Chapter
Chapter
1-40
RSTi Network Adapter Manual
User Manual - January 2012
GFK-2746
1
Command
Reaction to
Bus Fault
DP Clear Action
Word data
Format
Restart on Bus
fault
Hex
Binary
01 11
00000001
00010001
01: Clear Input
data
00: Bus Stop IO
fault action
01:MOTOROLA
01: auto reset
00 05
00000000
00000101
01: Clear Input
data
01: Bus Run (
clear Output)
00:INTEL
00:Power reset
00 15
00000000
00010101
01: Clear Input
data
01: Bus Run (
clear Output)
00:INTEL
01: auto reset
01 05
00000001
00000101
01: Clear Input
data
01: Bus Run (
clear Output)
01:MOTOROLA
00:Power reset
01 15
00000001
00010101
01: Clear Input
data
01: Bus Run (
clear Output)
01:MOTOROLA
01: auto reset
00 09
00000000
00001001
01: Clear Input
data
10: Bus Run (
Hold Output)
00:INTEL
00:Power reset
00 19
00000000
00011001
01: Clear Input
data
10: Bus Run (
Hold Output)
00:INTEL
01: auto reset
01 09
00000001
00001001
01: Clear Input
data
10: Bus Run (
Hold Output)
01:MOTOROLA
00:Power reset
01 19
00000001
00011001
01: Clear Input
data
10: Bus Run (
Hold Output)
01:MOTOROLA
01: auto reset
00 02
00000000
00000010
10: Stay with last
input
00: Bus Stop IO
fault action
00:INTEL
00:Power reset
00 12
00000000
00010010
10: Stay with last
input
00: Bus Stop IO
fault action
00:INTEL
01: auto reset
01 02
00000001
00000010
10: Stay with last
input
00: Bus Stop IO
fault action
01:MOTOROLA
00:Power reset
01 12
00000001
00010010
10: Stay with last
input
00: Bus Stop IO
fault action
01:MOTOROLA
01: auto reset
00 06
00000000
00000110
10: Stay with last
input
01: Bus Run (
clear Output)
00:INTEL
00:Power reset
00 16
00000000
00010110
10: Stay with last
input
01: Bus Run (
clear Output)
00:INTEL
01: auto reset
01 06
00000001
00000110
10: Stay with last
input
01: Bus Run (
clear Output)
01:MOTOROLA
00:Power reset
01 16
00000001
00010110
10: Stay with last
input
01: Bus Run (
clear Output)
01:MOTOROLA
01: auto reset
00 0A
00000000
00001010
10: Stay with last
input
10: Bus Run (
Hold Output)
00:INTEL
00:Power reset
00 1A
00000000
00011010
10: Stay with last
input
10: Bus Run (
Hold Output)
00:INTEL
01: auto reset
01 0A
00000001
00001010
10: Stay with last
input
10: Bus Run (
Hold Output)
01:MOTOROLA
00:Power reset
01 1A
00000001
00011010
10: Stay with last
input
10: Bus Run (
Hold Output)
01:MOTOROLA
01: auto reset
DPV1 Read service
Slot#=0, Index 1: Read STXPBS001 extension parameters (2Byte)
Slot#1~32, Index 1: Read parameter for an IO module.
Slot#1~32, Index 2: Read memory data from an IO module.
Slot#=0, Index 254: Read vendor code from EEPROM directly.