5-18
RSTi Network Adapter Manual User Manual -January 2012
GFK-2746
5
Force OFF-
is set for the Inputs Default at “IO device Access point tab for
successful operation.
b.
Hold Last Image
: Input values will be holding. NET LED will be Green.
Network adaptor communication with master intact. IO LED will be red
and fault “Loss/addition of device' logged in I/O fault table. Ensure that –
Hold last State-
is set for the Inputs Default at “IO device Access point tab
for successful operation.
c.
Auto Reset
: This option will reset the profinet Adapter module.
d.
Disconnect Profinet
: Last input values will not hold. NET LED will be
blinking Green. Network adaptor communication with master stops .IO
LED
ill be red and fault “Loss/addition of device' logged in I/O fault table.
Note:
Refer to the examples section in the power modules chapter in New Slice IO
manual for more details about the IO node configuration using the different power
modules.