P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE
APPLICATION EXAMPLE
4.
Verify that the data
Update mode
is “Cyclically” with default
Update time
of
100
×
10 ms = 1000 ms. This can be changed to any value between 10 ms (1
×
10 ms)
to 655350 ms (65535
×
10 ms).
Figure 9-23: Changing configuration parameters for a query
5.
Expand the
User memory map values (F1)
command in the
MM2 Meter
item and click
on
Query
. Set the configuration parameters as above.
6.
Expand the
Command Function code + operation code (F1, F22)
command in the
MM2 Meter
item and click on
Query
.
7.
Set the following configuration parameters.
Offline option for Fieldbus
= Freeze
Offline Options for sub-network
= Freeze
Upload mode
= On data change
Reconnect time
= 500 (5 sec)
Retries
= 5
Figure 9-24: Query parameters for the command function