GEK-113188A
MIGII Digital Protection for Electrical Machines
D-3
APPENDIX D
D.1 TRIP CIRCUIT SUPERVISION FOR MII-FAMILY RELAYS
D
D.1.1 SETTINGS AND CONFIGURATION
Settings and configuration related to this function are described below:
1.
Under I/O CONFIGURATION, Input#1 must be configured as 'General Input'. It will be used to monitor the permanent
presence of voltage.
2.
Under LOGIC CONFIGURATION, LOGIC#1, Invert Input#1 and set the timer to the time delay to produce the Trip
Circuit Supervision Alarm, for example 15 seconds
.