MIGII Digital Protection for Electrical Machines
GEK-113188A
9.15 GROUND TOC ELEMENT (51G)
9 RELAY COMMISSIONING
9
9.15GROUND TOC ELEMENT (51G)
Enable 51G element only and set its current pickup value to the minimum possible.
9.15.1 IEC INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 15.3 and 19.7 sec.
Apply 5 times the pickup current and the relay should trip between 4.1 and 4.5 sec.
9.15.2 IEC VERY INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 23.4 and 31.8 sec.
Apply 5 times the pickup current and the relay should trip between 3.1 and 3.6 sec.
9.15.3 IEC EXTREMELY INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 27 and 39 sec.
Apply 5 times the pickup current and the relay should trip between 1.5 and 1.85 sec
51G SETTINGS GROUP
Curve
INVERSE
Time Dial
1
51G SETTINGS GROUP
Curve
VERY INVERSE
Time Dial
1
51G SETTINGS GROUP
Curve
EXTREMELY INVERSE
Time Dial
0.5