GEK-113188A
MIGII Digital Protection for Electrical Machines
B-1
APPENDIX B
B.1 IEC/BS142 CURVES
B
APPENDIX B TIME-CURRENT CURVES FOR 51P AND 51N UNITSB.1IEC/BS142 CURVES
For 1<V<1.05 the unit will show a pickup signal and generate no trip.
For 1.05
V<20.00 trip time will be:
For V
20.00, trip time will be the same as for 20 times the setting:
Where:
Table B–1: GE IEC/BS142 INVERSE TIME CURVE CONSTANTS
CURVE NAME
A
P
Q
B
K
Extremely inverse
IEC Curve C
80
2
1
0
0
Very inverse
IEC Curve B
13.5
1
1
0
0
Inverse IEC
Curve
A
0.14
0.02
1
0
0
≤
≤