– 21 –
5 Burner Cooktop Models
Location
BTUs
Orifice Size
Burner Head
LF, LR
9,500
.89Lmm (II)
183D5612
CTR
9,500
.89Lmm (II)
183D5612
RR
5,000
.63Lmm (I)
183D5613
RF
11,000
.99Lmm (III)
183D5614
Install orifices and position burner caps as shown
99
89
89
Front
Medium
Medium
Large
63
Small
89
Medium
GEA00279
4 Burner Cooktop Models
Location
BTUs
Orifice Size
Burner Head
LF, LR
9,500
.89Lmm (II)
183D5612
RR
5,000
.63Lmm (I)
183D5613
RF
11,000
.99Lmm (III)
183D5614
63
99
89
89
Front
Medium
Medium
Large
GEA00280
Small
burner chimney as shown by number on the
above chart:
3. Place LP gas burner head onto chimney, as
indicated by number.
4. Place correct size burner caps onto burners,
then replace grates.
Convert the Pressure Regulator
WARNING:
Do not remove pressure regulator
from cooktop.
1. Locate pressure regulator under rear of
cooktop.
2. Use an adjustable wrench to remove nut from
pressure regulator.
LP
Nut
Gas flow into
range
LP adapter
GEA00257
NAT
3. Insert LP adapter into nut.
LP
adapter
Nut
LP
GEA00258
NAT
4. Reinsert assembly into regulator and attach tie-
on label to regulator using string provided.
Check for Leaks
WARNING:
Do not use a flame to check for leaks.
Check for leaks
before
attempting to light burners.
When all connections have been made, make sure
all cooktop controls are in the OFF position and
turn ON main gas supply valve. Use a liquid leak
detector at all joints and connections to check for
leaks in system.
Note:
When using test pressures greater than 1/2
psig to pressure-test the gas supply system of a
residence, disconnect cooktop and individual shut-
off valve from gas supply piping. When using test
pressures of 1/2 psig or less to test the gas supply
system, simply isolate cooktop from gas supply
system by closing individual shut-off valve.
Five-Burner Cooktop Models
Four-Burner Cooktop Models