CHAPTER 4: SETPOINTS
CONFIGURATION SETPOINTS
MM200 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
4–13
Auto LED Color
Range: None, Red, Green, Orange
Default: Orange
Selects the color of the Auto LED.
Manual LED Color
Range: None, Red, Green, Orange
Default: Orange
Selects the color of the Manual LED.
50% LED Color
Range: None, Red, Green, Orange
Default: Orange
Selects the LED color at 50% of the motor load.
80% LED Color
Range: None, Red, Green, Orange
Default: Orange
Selects the LED color at 80% of the motor load.
100% LED Color
Range: None, Red, Green, Orange
Default: Orange
Selects the LED color at 100% of the motor load.
Counters Settings
Drive Greasing Interval
Range: 100 to 50000 hours in steps of 100 hours
Default: OFF
This setpoint allows the user to set the alarm level for the greasing interval
Contactor Inspection Interval
Range: 0 to 64000 hours in steps of 100 hours
Default: OFF
This setpoint allows the user to set the alarm level for the contactor inspection interval.
Maximum Motor Stopped Time
Range: 10 to 10000 hours in steps of 10 hours
Default: OFF
This setpoint allow the user to set the alarm level for the maximum allowable motor
stopped hours.