4–2
MM200 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETPOINTS
CHAPTER 4: SETPOINTS
•
%UB: percent unbalance
•
Ctrl: control
•
Hr & hr: hour
•
O/L: overload
•
ops: operations
•
mcc: motor control center
Configuration setpoints
The configuration setpoints contains data on motor configuration as well as system setup,
inputs, outputs, communications, and CTs.
•
Motor (setpoints related to motor configuration).
•
CT (setpoints related to CT configuration).
•
Inputs (setpoints related to digital input configuration)
•
Outputs (setpoints related to digital output configuration)
•
Comms (setpoints related to communications configuration)
•
System (setpoints related to MM200 system configuration, such as the faceplate
LEDs)
•
Counters (setpoints related to the digital counters)
Motor setpoints
The MM200 starter function is responsible for executing the motor startup sequence,
including the pre-contactor start warning. The MM200 provides three pre-defined starters.
•
Full-voltage non-reversing
•
Full-voltage reversing
•
Two-speed
NOTE
NOTE:
By selecting a pre-defined starter, inputs and outputs are automatically assigned.
Common motor
setpoints
Several motor setpoints are dependent on the chosen starter type. The setpoints shown
below are common to all starter types.
Motor Name
Range: up to 20 alphanumeric characters
Default: Motor Name
This setpoint specifies a name for the motor. This name will appear in the actual values.
Starter Type (Mandatory setpoint)
Range: None, FV Non-Reversing, FV Reversing, Two Speed
Default: FV Non-Reversing
This setpoint selects the starter type. The relay is essentially disabled when the value is
set to “None”. Figure 1 illustrates typical starter timing beginning from the stopped state
for all starter types.