5- 10
Troubleshooting
5.11 Low Percent Rejection
The overall membrane performance can be affected by a number of factors. Poor
rejection performance, as well as high TDS, can result from fouled membranes, low
pump pressure, inadequate waste flow, or feed water problems. An apparent
performance problem could be caused by a defective sensor or circuit board, and not be a
membrane issue at all. The recommended first step for any ‘membrane performance’
question is to confirm the rejection percentage and product TDS with a hand-held
RO/TDS meter. If the product water quality is poor, investigate the membrane.
However, if the water quality tests ‘normal’, investigate the monitoring circuits.
1.
Waste flow too low.
a. Disinfectant or cleaner not rinsed from RO.
b. Check waste flow control.
c. Check for obstruction or kink in waste line.
2.
Pump pressure too low.
a. Adjust pressure regulator.
b. Adjust pump settings.
3.
Product flow too high.
a. See
5.9
4.
Membrane scaled or fouled.
a. Verify condition of pretreatment equipment.
b. See membrane cleaning procedure in this manual.
5.
Erroneous meter readout.
a. Verify water quality with independent meter and check conductivity probe
connection.
b. Check all quick-disconnect connections.
c. Replace inlet water sensor probe.
d. Replace product water sensor probe (percent rejection).
e. Replace monitor circuit board.
6.
Membrane failure.
a. Replace
membrane.
7.
Change in feed water TDS.
a. Verify feed and product water quality with independent meter.
b. Softener problem, rinsing out high levels of salt.
Summary of Contents for MILLENIUM OSMONICS MILLENIUMTM REVERSE OSMOSIS...
Page 2: ......
Page 6: ...14693e D D 31 March 2003 This page intentionally left blank...
Page 24: ...M Millenium RO System by GE Osmonics 14693e 31 Mar 03 1 18 General Information NOTES...
Page 36: ...M Millenium RO System by GE Osmonics 14693e 31 Mar 03 3 5 5 System Operation NOTES...
Page 67: ...M Millenium RO System by GE Osmonics 14693e 31 Mar 03 4 30 Routine Maintenance NOTES...
Page 80: ...M Millenium RO System by GE Osmonics 14693e 31 Mar 03 5 13 Troubleshooting NOTES...
Page 85: ...M Millenium RO System by GE Osmonics 14693e 31 Mar 03 6 4 Drawings Millenium RO Disinfect View...
Page 86: ...M Millenium RO System by GE Osmonics 14693e 31 Mar 03 6 5 Drawings Millenium RO Flow Schematic...
Page 98: ...M Millenium RO System by GE Osmonics 14693e 31 Mar 03 6 17 Drawings NOTES...
Page 105: ...M Millenium RO System by GE Osmonics 14693e 31 Mar 03 7 6 Spare Parts List NOTES...
Page 106: ......