Plus rM and
PM™
Units
2.
Mode
!:N
' .,
f Lf
SETUP
PICKUP
Figure
26.
Trip Unit display for voltage-unbalance relay pickup.
Voltage-Unbalance Relay Delay
This function sets the delay time before a voltage
unbalance trip occurs. The range of delays is 1 to 1 5
seconds, in steps of 1 second. Choosing
O F F
disables
voltage-unbalance protection. The Trip Unit display
is shown in Figure 27.
' "
f.Lf
s
SETUP
DELAY
Figure
27.
Trip Unit display for voltage-unbalance relay delay.
Current-Unbalance Relay Pickup
This function compares the true RMS current in the
highest or lowest phase with the average of all three
phases and initiates a trip if the difference exceeds
the set point. The range of set points is 1 0 to 50% of
the unbalance, with an increment of 1 % . The Trip
Unit display is shown in Figure 28.
' .,
f Lf
PICKUP
SETUP
Figure
28.
Trip Unit display for current-unbalance relay pickup.
Current-Unbalance Relay Delay
This function sets the delay time before a current
unbalance trip occurs. The range of delays is 1 to 15
seconds, in steps of 1 second. Choosing
O F F
disables
20
current-unbalance protection. The Trip Unit display
is shown in
29.
L11
' .,
f.Lf
SETUP
s
DELAY
Figure
29.
Trip Unit display for current-unbalance relay delay.
Undervoltage Relay Pickup
This function measures the true rms voltage in all
phases and initiates a trip if any phase voltage drops
below the set point. The range of set points is 50 to
90% of the nominal voltage, with an increment of
1 % . The Trip Unit display is shown in Figure 30.
SETUP
V<
PICKUP
Figure
30.
Trip Unit display for undervoltage relay pickup.
Undervoltage Relay Zero-Volt Trip Enable
This function determines if the relay trips when all
three phase voltages drop to zero volts. The Trip
Unit display for zero-volt trip disabled is shown in
Figure 3 1 . The Trip Unit display for zero-volt trip
enabled is shown in Figure 32.
., VOLTS
SETUP
l..f
V<
Figure
31.
Trip Unit display for undervoltage relay zero-volt trip
disabled.