SPECIFICATIONS - continued
GEH-7252
6
May 2003
g
GE Capacitor & Power Quality Products
Ambient Temperature (Operating)
Enclosed Filters:
-40 to +40 degrees C
Open Panel Filters:
-40 to +50 degrees C
Storage Temperature:
-40 to +90 degrees C
Altitude: 0 to 3300 Feet above sea level. Refer to Figure 6 for altitude derating.
Relative Humidity: 0 to 95% non-condensing
Agency Approvals
UL-508C
File E191686 Component Recognized
(3-1000 HP, 120 VAC through 600 VAC
50, 50/60, 60 Hz Three Phases
CAN/CSA
C22, 2 No. 14-95
Performance
Total Harmonic Current Distortion:
Eight Percent Filter: 8% typical at full load
12% maximum no load to full load
Five Percent Filter: 5% typical at full load
8% maximum no load to full load
Standby Current:
Without Optional Capacitor Contactor: 70% of the full load capacitor current listed in Table 3
With Optional Capacitor Contactor: Refer to Drive Users Manual
8% Filter Voltage Regulation with nominal 480 volts RMS source
Maximum output voltage at no load: 502 volts RMS, 710 volts peak
Maximum PCC* voltage with 6.00% source impedance at no load: 490 volts RMS, 693 volts peak
Minimum output voltage at full load: 460 volts RMS, 600 volts peak
5% Filter Voltage Regulation with nominal 480 volts RMS source
Maximum output voltage at no load: 502 volts RMS, 710 volts peak
Maximum PCC voltage with 6.00% source impedance at no load: 490 volts RMS, 693 volts peak
Minimum output voltage at full load: 460 volts RMS, 600 volts peak
*Note: PCC is the point of common coupling with the power distribution system