Masoneilan SVI FF Positioner Quick Start Guide
=
|
15
Step 3: Basic Configuration
This section serves as an example where the AO block and TB block are configured. However,
there are a number of combinations that can be configured. This discussion is valid if the posi-
tioner is controlled by the AO block.
1. For the Transducer block set:
ACTUATOR_3.ACT_FAIL_ACTION_1 = either
1. Valve Closed
(most common) or
2. Valve Open
ACCESSORY.REMOTE_SENSOR = 0, if remote sensor is not in use (internal
Hall sensor is used)
ACTIVATE_CONTROL_SET to one of:
0
: Activate Custom
Control Set
(required for Auto-
tune as well - most
common)
1
: Activate Control
Set 1 (Slowest)
2
: Activate Control
Set 2
3
: Activate Control
Set 3
4
: Activate Control
Set 4
5
: Activate Control
Set 5 (Fastest)
6:
Activate Control
Set 6 (Double Acting
- Slow)
7
: Activate Control
Set 7 (Double
Acting- Fast)
CHAR_SELECTION.TYPE to one of:
0
. Linear (most
common)
1
. Equal Percent-
age (30:1)
2
. Equal Percent-
age (50:1)
3
. Quick Open
(reversal from Equal
Percentage (50:1))
4
. Custom
5
. Camflex
Percentage
See
Transducer Block
Parameters
in the SVI FF instruction manual for further
settings.
2. For the AO block review/set as below:
PV_SCALE.UNIT
INDEX =
%
XD_SCALE.UNIT
INDEX =
%
CHANNEL =
Position
SHED_OPT =
NORMAL SHED
NORMAL RETURN