GE Power Management
LPS-O Line Protection System
2-
53
2 CALCULATION OF SETTINGS
2.5 REFERENCE TABLES
2
TABLE NOTES:
* The IPB and IPT settings are fixed as shown and are NOT adjustable by the user.
†
Contact is normally open; add 1000 to number to close contact under normal conditions
1620
C2
(configurable)
C2 Contact
0 to 256 step 1
†
0 to 256 step 1
†
1621
KT1
(configurable)
KT1 Contact
0 to 256 step 1
†
0 to 256 step 1
†
1622
KT2
(configurable)
KT2 Contact
0 to 256 step 1
†
0 to 256 step 1
†
1623
KT3
(configurable)
KT3 Contact
0 to 256 step 1
†
0 to 256 step 1
†
1624
KT4
(configurable)
KT4 Contact
0 to 256 step 1
†
0 to 256 step 1
†
1625
CONFTRIP
Initiate Three phase Trip with
Input from Xpression Builder
0 to 256 step 1
†
0 to 256 step 1
†
1626
CONFOSC
Initiate Oscillography Capture
with Xpression Builder Input
0 to 256 step 1
†
0 to 256 step 1
†
Table 2–9: PROTECTION SETTINGS DATA SHEET (Sheet 7 of 7)
No.
M nem onic
Description
Range (5A)
Range (1A)
User
Setting
see TABLE NOTES on page 2–53 for footnote explanations
Summary of Contents for LPS-O
Page 2: ......
Page 4: ......
Page 14: ...x LPS O Line Protection System GE Power Management TABLE OF CONTENTS ...
Page 208: ...9 8 LPS O Line Protection System GE Power Management 9 3 TROUBLESHOOTING 9 SERVICING 9 ...
Page 226: ...10 18 LPS O Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Page 288: ...B 4 LPS O Line Protection System GE Power Management B 2 FIGURES APPENDIXB B ...
Page 292: ...C 4 LPS O Line Protection System GE Power Management C 1 KEYPAD MENUS APPENDIXC C ...
Page 294: ...D 2 LPS O Line Protection System GE Power Management D 1 WARRANTY INFORMATION APPENDIXD D ...
Page 306: ...xii LPS O Line Protection System GE Power Management INDEX INDEX ...
Page 307: ...GE Power Management LPS O Line Protection System NOTES ...