GE Power Management
LPS-O Line Protection System
9-
3
9 SERVICING
9.2 SERVICING WITH THE RELAY SELF-TEST
9
Table 9–2: RUN-TIME BACKGROUND SELF-TESTS
Component
Method
Processor
Nature
Flash Memory (PROM)
CRC-type check
960 CPU
Critical, restart
EPROM
Checksum type check
DSP
Critical, restart
RAM
Protection values checked for
correctness; Configurable logic checked
for validity
960 CPU
Critical, restart
Nonvolatile RAM
CRC-type check on settings area
960 CPU
Non-critical
CAPRAM
Checksum on fault storage area
960 CPU
Table 9–3: RUN-TIME FOREGROUND SELF-TESTS
Component
Method
Processor
Nature
A/D Controller
DMA interface
960 CPU
Critical
Digital Input Circuitry
Comparison of bits read via two separate
optocouplers
960 CPU
Non-critical, turn off
pilot protection
Digital Output Circuitry
Loop-back test
960 CPU
Critical, restart
Trip Circuit Continuity
Bit read via bus
960 CPU
Non-critical
LUI
Operator initiated, visual feedback
960 CPU
Non-critical
Summary of Contents for LPS-O
Page 2: ......
Page 4: ......
Page 14: ...x LPS O Line Protection System GE Power Management TABLE OF CONTENTS ...
Page 208: ...9 8 LPS O Line Protection System GE Power Management 9 3 TROUBLESHOOTING 9 SERVICING 9 ...
Page 226: ...10 18 LPS O Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Page 288: ...B 4 LPS O Line Protection System GE Power Management B 2 FIGURES APPENDIXB B ...
Page 292: ...C 4 LPS O Line Protection System GE Power Management C 1 KEYPAD MENUS APPENDIXC C ...
Page 294: ...D 2 LPS O Line Protection System GE Power Management D 1 WARRANTY INFORMATION APPENDIXD D ...
Page 306: ...xii LPS O Line Protection System GE Power Management INDEX INDEX ...
Page 307: ...GE Power Management LPS O Line Protection System NOTES ...