GE Digital Energy
g
LanPro
®
5/6/8/10-11U installation drawings
Model
Heat dissipation
Linear load 240 Volt
Dimensions
Air flow
100%
load
Rel.
humidity
non-cond.
Altitude
(max 4000m)
Input wiring
Output wiring
100% load
50% load
h
w
d
Weight
Amb.
temp.
utility volt.
120V
utility volt.
208V
utility volt.
240V
output
volt. 120V
output
volt. 208V
output
volt. 240V
LanPro
W
Btu/hr
W
Btu/hr
Inch
Inch
Inch
Lbs
m3/hr
°F
m
AWG/mm
2
AWG/mm
2
AWG/mm
2
AWG/mm
2
AWG/mm
2
AWG/mm
2
5-11U
571
1950
389
1329
26.8
12.3
28.7
295
660
14-104
<95
N.A.
10/6
10/6
8/10
10/6
10/6
6-11U
661
2254
381
1300
26.8
12.3
28.7
295
660
14-104
<95
N.A.
8/10
10/6
8/10
10/6
10/6
8-11U
948
3234
551
1882
26.8
12.3
28.7
386
660
14-104
<95
N.A.
6/14
8/10
6/14
8/10
8/10
10-11U
1090
3719
556
1896
26.8
12.3
28.7
410
660
14-104
<95
N.A.
4/22
6/14
4/22
8/10
8/10
5-11U/120 V
641
2187
425
1451
39.2
12.3
28.7
386
660
14-104
<95
6/14
N.A.
N.A.
8/10
10/6
10/6
6-11U/120 V
744
2539
601
2051
39.2
12.3
28.7
386
660
14-104
<95
<1000, derating
12.5% per 1000
4/22
N.A.
N.A.
8/10
10/6
10/6
Model
Minimum free space required
(Inches)
front side rear
Distance between mounting
holes (Inches)
Input overcurrent protection
(AMPS)
Output overcurrent protection (AMPS)
x
y
z
120V
208V
240V
120V
(1 X)
120V
(2X)
208V
240V
L5-11U
4
2
8
7.24
22.76
7.48
35
30
40
20
25
20
L5-11U /120V
4
2
8
7.24
22.76
7.48
60
40
20
25
20
L6-11U
4
2
8
7.24
22.76
7.48
40
35
50
25
30
25
L6-11U /120V
4
2
8
7.24
22.76
7.48
70
50
25
30
25
L8-11U
4
2
8
7.24
22.76
7.48
60
45
70
35
40
35
L10-11U
4
2
8
7.24
22.76
7.48
70
60
80
40
50
40