LX: OPM_LPA_11U_5K0_10K_1US_V021
39
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
GE Digital Energy
g
UPS Type
:
L5-11U
L6-11U
L8-11U
L10-11U
Output power (kVA/kW)
:
5/4
6/4.8
8/6.4
10/8
AC input voltage
:
120/208/240 Vac (120V only with step-up transformer for L5/6-11U)
Input frequency
:
60/50 Hz
AC output voltage
:
120/208/220/230/240V
Output frequency
:
60 or 50 Hz, std. 60 Hz; selectable on front
System efficiency (full load)
:
87%
Line input breaker (C-type)
:
32A
32A
50A
63A
Bypass input breaker (C-type)
:
32A
32A
50A
63A
Battery safety fuse (F4A)
:
30A
30A
30A
30A
Battery safety fuse (F4B)
:
30A (spare)
30A (spare) 30A
30A
Internal safety fuse (F5A)
:
-
-
30A
30A
Internal safety fuse (F5B)
:
30A
30A
30A
30A
Input/output connectors
:
terminals at rear of unit
INPUT
AC input voltage range (208V-240V)
at 100% load
:
162 - 285 V
at 50% load
:
146 - 285 V
at 20% load
:
133 - 285 V
AC input voltage range (120V, L5/6-11U)
at 100% load
:
81 - 141 V
at 50% load
:
72 - 141 V
at 20% load
:
66 - 141 V
Input frequency range
:
40-70 Hz
Input current wave form
:
sinusoidal
Input power factor
:
≥
0.99
Max. input current at 100% load
120V :
43.3A
50.8A
n.a.
n.a.
208V :
25.0A
30.0A
40.5
50.3
240V :
21.4A
25.1
34.8
42.0
Inrush current
:
none
Rectified DC voltage out
:
380 V
BATTERY CHARGER
Characteristic
:
U/I-characteristic, constant current charging until boost/float voltage, then
constant voltage charging and boost charge mode for fast recharging of batteries
DC input voltage range
:
350-450 V
DC output voltage at 20 °C
:
float: 273 V boost: 295 V
Output current limit (Adc)
:
2.0
2.0
3.0
3.0
OUTPUT CONVERTER
Output power at pf. = 0.8, VA*
:
5000
6000
8000
10000
Semiconductor
:
IGBT
AC output voltage
:
120/208/240V ± 1% static resistive load
120/208/240V ± 2% measured crest load 2.5:1
120/208/240V ± 2% dynamic mean deviation over one half cycle for 100% of
rated load applied or removed
Typical overload
:
110%
≥
20 minutes
(temp. dependent)
130%
≥
3.5 minutes
150%
≥
2 minutes
Output frequency
:
60 or 50 Hz selectable, ± 0.1%, unless synchronized with the utility
Freq. tracking range
:
± 2/4/6% of nominal, user selectable
Output wave form
:
sine wave
Max. phase difference input-output
:
max 7
°
Harmonic distortion
:
2% max. with linear load
Power factor range
:
Any lagging or leading power factor permitted within the specified rating to pf. 0.5
Output derating altitude
:
Till 1000m no derating
Above 1000m 12.5% per 1000m, max. 4000m
Protection
:
Automatic shut down (or transfer to bypass, if bypass is available) in case of
- low/high DC voltage
- overtemperature
- overload / short circuit
The output is protected against connection to the utility supply
* according to EN 50091-1
10 - Specifications