34
Installation Instructions
ELECTRICAL CONNECTIONS
Electrical Requirements
120-volt, 60 Hertz, properly grounded branch circuit
protected by a 15-amp or 20-amp circuit breaker or
time delay fuse.
Extension Cord Cautions
Because of potential safety hazards associated with
certain conditions, we strongly recommend against
the use of an extension cord. However, if you still
elect to use an extension cord, it is absolutely
necessary that it be a UL-listed, 3-wire grounding-
type appliance extension cord and that the current
carrying rating of the cord in amperes be equivalent
to, or greater than, the branch circuit rating.
Grounding
IMPORTANT—(Please read carefully)
FOR PERSONAL SAFETY, THIS APPLIANCE MUST
BE PROPERLY GROUNDED.
The power cord of this appliance is equipped
with a 3-prong (grounding) plug which mates with a
standard three-prong grounding wall receptacle to
minimize the possibility of electric shock hazard from
this appliance.
The customer should have the wall receptacle and
circuit checked by a qualified electrician to make sure
the receptacle is properly grounded.
Where a standard two-prong wall receptacle is
encountered, it is the personal responsibility and
obligation of the customer to have it replaced with a
properly grounded three-prong wall receptacle.
DO NOT, UNDER ANY CIRCUMSTANCES, CUT OR
REMOVE THE THIRD (GROUND) PRONG FROM THE
POWER CORD.
A word about GFCI’s – GFCI’s are not required or
recommended for gas range receptacles.
Ground Fault Circuit Interrupters (GFCI’s) are
devices that sense leakage of current in a circuit and
automatically switch off power when a threshold
leakage level is detected. These devices must be
manually reset by the consumer. The National
Electrical Code requires the use of GFCI’s in kitchen
receptacles installed to serve countertop surfaces.
Performance of the range will not be affected if
operated on a GFCI-protected circuit but occasional
nuisance tripping of the GFCI breaker is possible.
3
ELECTRICAL CONNECTIONS
(CONT.)
Usage Situations where Appliance Power
Cord will be Disconnected Infrequently.
An adapter may be used only on a 15-amp
circuit. Do not use an adapter on a 20-amp
circuit. Where local codes permit, a
TEMPORARY CONNECTION
may be made to a
properly grounded two-prong wall receptacle
by the use of a UL-listed adapter, available at
most hardware stores. The larger slot in the
adapter must be aligned with the larger slot in
the wall receptacle to provide proper polarity in
the connection of the power cord.
When disconnecting the power cord from the
adapter, always hold the adapter with one hand.
If this is not done, the adapter ground terminal
is very likely to break with repeated use. Should
this happen,
DO NOT USE
the appliance until a
proper ground has again been established.
A
3
Preferred Method
Ensure proper
ground exists
before use
Temporary Method
Ensure proper
ground and firm
connection before
use
Align large prongs/slots
CAUTION:
Attaching the adapter
ground terminal to the wall receptacle cover
screw does not ground the appliance unless
the cover screw is metal, and not insulated,
and the wall receptacle is grounded through
the house wiring. The customer should have
the circuit checked by a qualified electrician to
make sure the receptacle is properly grounded.