background image

 

 

© 2003 GE Interlogix B.V.  

xxxxxxx 

 

All Rights Reserved 

12/2004 

    

  

  

  

  

  

  

  

  

  

  

  

 

 

 

4/8-Zone DGP  

 

 

M

OUNTING THE UNIT

 

The PCB can be mounted in any existing ATS series enclosure 
that supports the BB format.Connections  

J1 

COMMS 

12 VDC power supply. It is recommended that where 
the distance between an ATS1220 and the nearest 
device is more than 100 meters, a separate power 
supply be used. 

COMMS 

Positive and negative data connection of the system 
databus. Units can be up to 1.5 km from the 4-lift 
DGP or the ATS control panel, depending on the 
cable used. See the ATS control panel installation 
guide for details. 

TAMP 

Connect the enclosure tamper switch across  
these terminals (Tamper switch requires  
normally open contacts.) 

J2/J3 

Each zones requires a 4k7 end-of-line resistor (1 or 2  
depending on single or dual zone monitoring programmed  
in ATS control panel). 

J4 

+12 VDC supply and open collector or data output for output 
connection to ATS 1810, ATS 1811 and ATS 1820 output cards 
via 10-way cable supplied with the output card. Up to sixteen 
outputs are available with 8-way or 16-way open collector cards  
(4-way and 8/16-way output cards cannot be used together  
on the same DGP) 

L

INKS

 

 

Earth connection. Earth wires from all pieces of 
equipment must be earthed at one system earth.  
For further detail see the ATS control panel  
installation guide. 

“I

NT

./E

XT

. T

AMP

” J

UMPER 

S

ETTINGS 

}

 

INT 

Tamper switch SW4 + switch on backside SW5 of 
the PCB are used (eg. in combination with ATS1644, 
plastic housing). 

EXT 

Tamper connections on connector J1 (T, C) are 
used for an external tamper switch (eg. In 
combination with ATS1643, metal housing).  

DGP 

DIPSWITCH SETTINGS 

 

ADDR 

{

 

Dip switches 1 to 4 are used to identify the DGP 
number. 

ABCT 

|

 

 

Set switch T on if this device is the last device on the 
system databus. For more details see the ATS 
control panel installation guide. 

A,C 

Not in use 

ON - ATS1811 8-way relay card or ATS1820 16-way 
open collector card connected to J4.OFF - no 
ATS1811 or ATS1820 connected to J4. Use this 
setting also if an ATS1810 is connected to J4.  

Z

ONE NUMBERING

 

A 4/8-zones DGP can have four or eight zones connected to it. 
There are 16 zones allocated to every DGP address. Only zones 1 
to 4 or 1 to 8 can be used when an ATS1210/1211/1220 is 
allocated a DGP number. Zones not available (5 - 16) or (8-16) 
should be programmed as type 0 (zone disabled) in the Zone 
database. 

Control panel 

1 – 16 

DGP8 

129 - 144 

DGP1 

17 - 32 

DGP9 

 145 - 160 

DGP2 

33 - 48 

DGP10 

 161 - 176 

DGP3 

49 - 64 

DGP11 

 177 - 192 

DGP4 

65 - 80 

DGP12 

 193 - 208 

DGP5 

81 - 96 

DGP13 

 209 - 224 

DGP6 

97 - 112 

DGP14 

 225 - 240 

DGP7 

113 - 128 

DGP15 

 241 - 256 

Note 1:The ATS1210/1211/1220 cannot be expanded  to provide 
additional zones. 

ATS1210/1211/1220 

4/8-Zone DGP


D+ 
D- 

T

Summary of Contents for Interlogix ARITECH ATS1210

Page 1: ...rthed at one system earth For further detail see the ATS control panel installation guide INT EXT TAMP JUMPER SETTINGS INT Tamper switch SW4 switch on backside SW5 of the PCB are used eg in combinatio...

Page 2: ...tallation de la centrale ATS A C Non utilis B ON carte 8 relais ATS1811 ou carte 16 collecteurs ouverts ATS1820 connect e J4 OFF aucune carte ATS1811 ou ATS1820 connect e J4 Utiliser ce r glage si une...

Page 3: ...propriati CONNESSIONI J1 COMMS Alimentazione da 12 V Si consiglia di usare un alimentatore separato quando la distanza tra un ATS1210 1211 1220 e l apparato pi vicino superiore a 100 metri COMMS Conne...

Page 4: ...a znale w podr czniku instalacji centrali ATS TAMP Do tych zacisk w nale y pod czy styk sabota owy obudowy styk sabota owy musi mie styki normalnie otwarte J2 J3 Ka da linia wymaga rezystora ko ca lin...

Page 5: ...T C s o utilizados para liga o de um switch de tamper externo ex em conjunto com ATS1643 caixa met lica CONFIGURA ES DO DIPSWITCH DO DGP ADDR Os Dip switches 1 a 4 s o utilizados para identificar o n...

Page 6: ...ATS sentralapparatet Hvis RX LED en blinker men TX LED en ikke gj r det er ikke US programmert til bli pollet i sentralapparatet eller s er den adressert feil DGP de 4 8 zonas MONTAJE DE LA UNIDAD Mon...

Page 7: ...g og open collector udgang eller dataudgang for tilslutning til ATS 1810 ATS 1811 og ATS 1820 udgangskort via 10 leder kabel der f lger med udgangskortet Der er op til seksten udgange tilg ngelige med...

Page 8: ...mer Sektioner som inte r tillg ngliga 5 16 eller 8 16 ska programmeras som typ 0 sektionen avaktiverad i sektionsdatabasen Centralapparat 1 16 DGP8 129 144 DGP1 17 32 DGP9 145 160 DGP2 33 48 DGP1 161...

Page 9: ...ol hteen v linen et isyys on yli sata metri virtal hteen on suositeltavaa k ytt erillist tehol hdett COMMS J rjestelm n datav yl n positiivinen ja negatiivinen dataliit nt K ytett v st kaapelista riip...

Page 10: ...kautta Jos LED valo ei vilku keskuslaite ei ole toiminnassa tai datav yl tavallisesti kaapeli on viallinen TX Vilkkuva LED valo n ytt ett keskitin vastaa ATS keskuslaitteelta tulevaan pollaukseen Jos...

Page 11: ...A2 1998 A14 2000 EN61000 3 3 1995 EN60950 1992 A1 1993 A2 1993 A3 1995 A4 1997 A11 1997 CTR21 1998 EG201121 1998 Equipment class identifier RF products falling under the scope of R TTE X Not Applicabl...

Page 12: ...t rrelse H x B kortst rrelse B Dimensiones alto x ancho placa de tama o B 90 x 80 mm Wymiary obudowy metalowej WxSxD Dimens es da caixa met lica AxLxP Dimensjoner metal kapsling HxBxL Dimensiones caja...

Reviews: