GFK-2571A
Chapter 3 Configuration
3-7
3
Configuring PROFINET Controller Parameters
Configure the PNC parameters by editing the tabs as appropriate. The parameters are divided
among the tabs, and the options are available in the Inspector view.
PROFINET Controller Parameters (Settings Tab)
Status Address, Length:
The Status Address is the reference memory location for the PNC
’s 32
bits of status data. The Status address can be assigned to valid %I, %Q, %R, %AI, %AQ, %W, %G,
%T or %M memory by right-clicking on the Status Address field and selecting the Data Entry tool.
The default value is the next available %I address. See chapter 5,
Diagnostics
, for definitions of the
status bits that the module writes to this address.
Note:
Because point faults are not supported with %G, %T and %M, the other memory types or I/O
Symbolics are preferred.
SFP Cage 1 / 2 / 3 / 4:
If the module will use plug
–in Small Form-factor Pluggable devices as ports 3
and/or 4, specify the SFP devices in the appropriate field(s). On the Settings tab, right-click in the
Values field for the port, and select Data Entry Tool to open the Catalog window. In the Catalog
window, select the type of SFP device for the port, like the example shown below, and click OK. If
the device is not listed, choose GENERIC_SFP to add it to the configuration.